Honeywell CIU 888 Configuration Manual page 234

Hide thumbs Also See for CIU 888:
Table of Contents

Advertisement

Part No.: 4417584_Rev12
Appendix H - Creation of new Modbus field device / TRL/2 Field Device
XML Tag
<DeviceInformation>
<ModbusMap>
<Status>
< NoofModbusRegisters >
<DeviceInformation>
<ModbusMap>
<Status>
<ModbusDataType>
<DeviceInformation>
<ModbusMap>
<Status>
<ByteOrder>
<DeviceInformation>
<ModbusMap>
<Status>
<WordOrder>
H.17 Custom Value Map
This configuration defines the value mapping between device
parameter value and CIU parameter value. This configuration would be
defined only if a direct mapping of device parameter value to CIU
Configuration Manual
CIU 888
Description
This indicates the number of
Modbus registers defined for
the Modbus field device
status parameter that needs
to be scanned by CIU 888.
This indicates the Modbus
datatype for the Modbus
field device status parameter
that needs to be scanned by
CIU 888.
This indicates the Modbus
field device's byte order for
16 bit status data. Based on
this configuration, CIU 888
inteprets the field device
status value with correct
byte ordering.
There can be 2 formats in
which data can be exposed
(i) LSB first (ii) MSB first.
Based on this configuration
CIU interprets the data and
converts it to its internal data
format.
This indicates the Modbus
field device's word order for
32 bit status data. Based on
this configuration, CIU 888
interprets the field device
status value with correct
word ordering.
There can be 2 formats in
which data can be exposed
(i) LSW first (ii) MSW first.
Based on this configuration
CIU interprets the data and
converts it to its internal data
format.
Possible Values
As per Modbus
field device
Modbus datasheet
Not a number
Fixed number
8-bit unsigned
integer
8-bit signed integer
16-bit unsigned
integer
16-bit signed
integer
12-bit signed
integer
32-bit signed
integer
LSB_First
MSB_First
LSW_First
MSW_First
H - 48