Part No.: 4417584_Rev12
Getting Started
5. Click the BPM Field Port tab, the Properties detail appears.
You can view or edit these properties:
Properties
Sensitivity
Baud rate
Turn around delay
Time out
Retries
6. Click the RS Field Port tab, the Properties detail appears.
You can view or edit these properties:
Properties
Baud rate
Mode
Turn around delay
Configuration Manual
CIU 888
Description
Enter sensitivity in the range of 1 through 7 (default =
7).
Select 1200, 2400, or 4800.
When CIU 888 receives a response from a field instru-
ment (in a field port) it waits for this time period before
sending a new request on the same field port.
Enter time in ms (default = 20 ms).
Enter timeout in ms (default = 250 ms).
Enter number of retries in the range of 1 through 10
(default = 3).
Description
Select 1200, 2400, 4800, 9600, 19200, or 38400
Select RS 232 or RS 485 (default = RS-232C).
Enter reply waiting time in ms (default = 20 ms).
3 - 33