NOTE: Generate INI files from CIU B by connecting via service/VPN port.
NOTE: a) Entis pro automatically issues switch over if CIU B had taken value 1-99 in
NOTE: a) Entis pro automatically issues switch over if CIU A had taken value 1-99 in
NOTE: CIU A will restart and take up Passive role with Hot standby value 100.
Part No.: 4417584_Rev12
Updating CIU 888 Site configuration
If Entis Pro is the host then reload INI files. If Entis is used as host then reload
the site DB in Entis.
hot standby window on step 3. After switch over, CIU A will take value as 1-99
and role as Passive and CIU B will take value 100 and role as Active.
b) If both the CIUs (A and B) have value as 100, then user has to make CIU B
as Active by issuing a switch over command.
4. If configuration change is working as intended, skip to step 7.
5. Configuration change is not working as intended.
If the Host is Entis Pro then connect to CIU A via service/VPN port
and generate and reload INI files.
If the Host is ENTIS then reload the site DB in Entis.
hot standby window on step 5. Now CIU A will become active and take value as
100 and CIU B will become passive and take value as 1-99.
b) If both the CIUs (A and B) have value as 100, then user has to make CIU A
as Active by issuing a switch over command.
6. Make configuration changes in Service Tool/Ensite Pro revert the
configuration. Go to step 3.
7. Configuration update works as intended. Login to Active CIU (CIU B)
web interface and enable configuration sync. This will restart the
partner CIU A
8. Issue a switch over in Entis Pro. CIU A takes up Active role and CIU
B will take up Passive role.