NOTE: CIU B remains Passive with value 100 or 1-99 in hot stand by window.
NOTE: Generate INI files from passive CIU B by connecting via service/VPN port.
NOTE: a) Entis pro automatically issues switch over if CIU B had taken value 1-99 in
Part No.: 4417584_Rev12
Updating CIU 888 Site configuration

6.9.2 Updating configuration for Non-Restart parameters

This section covers the configuration update procedure that does not
involve restart of CIU 888.
1. Login to CIU A webpage and disable configuration synchronization.
Proceed to the next step on seeing "configuration sync is disabled
successfully" message.
2. Make configuration changes in service tool/Ensite Pro tool.
3. Update configuration to CIU B by connecting via service/VPN port.
If Entis Pro is the host then reload INI files. If Entis is used as host then reload
the site DB in Entis.
hot standby window on step 3. After switch over, CIU A will take value as 1-99
and role as Passive and CIU B will take value 100 and role as Active.
b) If both the CIUs (A and B) have value as 100, then user has to make CIU B
as Active by issuing a switch over command.
4. If configuration change is working as intended, skip to step 7.
5. Configuration change is not working as intended.
If the Host is Entis Pro then connect to CIU A via service/VPN port
and generate and reload INI files.
If the Host is ENTIS then reload the site DB in Entis.
Configuration Manual
CIU 888
6 - 6