FIGURE 5-5
FIGURE 5-6
Part No.: 4417584_Rev12
Commissioning of a Redundant System Setup
3. Highlight the Preferred secondary option using the navigation keys
and then press the OK key.
The Confirm Changes screen is displayed.
CIU 888 display: Confirm Changes screen
4. Highlight the OK option using the display keys. Click OK key.
The secondary CIU 888 is reset to the factory settings and reboots
twice. Because the Entis Pro system(s) connected to the CIU 888s is
shutdown, redundancy switchover is disabled during reboot.
5. Connect the PC/Laptop to the secondary CIU 888. Log on to the
secondary CIU 888 and change the initial password, refer to
section 4.2.1.
6. Verify the CIU 888 license, refer to section 4.2.2.
When commissioning of both the primary CIU 888 and secondary
CIU 888 is completed, the role of each CIU 888 in the redundant
system setup is indicated in the Status Dashboard (see FIGURE 5-
6).
Status Dashboard of primary CIU 888 (left) and secondary CIU 888 (right)
Configuration Manual
CIU 888
5 - 5