NOTE: Click the Apply button after filling details in Tanks, Entities, Temperature
3.2.14.2 Delete TCP/IP Modbus map
Part No.: 4417584_Rev12
Getting Started
Fields
Absolute start address
Temperature Profile Abso-
lute Start address
Temperature Profile
Record Interval
Density Profile Absolute
Start address
Density Profile Record
Interval
6. Enter the details as required and click Apply.
Profiles and Density Profiles tab.
On the CIU 888 node, right-click and select Delete exisiting TCP/
IP modbus map from the menu.
Configuration Manual
CIU 888
Description
This indicates the absolute start address of the Modbus
tank record.
Values are in decimal.
Note: For Entis Pro and ENTIS Complaint Modbus
mapping, if the number of tanks are more than 50 then
configure absolute start address as 10000.
This indicates the absolute start address of the tem-
perature profiles record.
Values are in decimal. Default value is 20000. Configu-
rable when modbus mapping is User Specified.
This indicates the record interval of the temperature
profiles record.
Values are in decimal. Default value is 125. Configu-
rable when modbus mapping is User Specified.
This indicates the absolute start address of the density
profiles record.
Values are in decimal. Default value is 30000.
Configurable when modbus mapping is User Specified.
This indicates the record interval of the density profiles
record.
Values are in decimal. Default value is 320.
Configurable when modbus mapping is User Specified.