Honeywell CIU 888 Configuration Manual page 64

Hide thumbs Also See for CIU 888:
Table of Contents

Advertisement

Part No.: 4417584_Rev12
Getting Started
Properties
Time-out
Stop bits
Parity
Duplex mode
Retries
7. Click the TRL2 Field Port tab, the Properties detail appears.
You can view or edit these properties:
Properties
Baud rate
Turn around delay
Time-out
Stop bits
Parity
Retries
3.2.6.2 Ethernet Field Port
On CIU 888 node click FTEA port.
By default FTE tab appears displaying various properties
Configuration Manual
CIU 888
Description
Enter timeout in ms (default = 250 ms).
Note: For Modbus field ports, the default timeout of 250
ms might not be sufficient in case of lower baud rates
(1200, 2400 etc.,) and needs to be increased.
Calculate the field port timeout as Field port timeout =
(1000 / baud rate) * No of bits in a byte * Maximum
number of bytes retrieved from Modbus device in a
single request ms and configure it accordingly.
Select 1 or 2 (default = 1).
Select Odd, Even, or None (default = Odd).
Select Full or Half (default = Full).
Enter number of retries (default = 3)
Description
Baud rate is fixed and not editable (default = 4800 ms).
Enter reply waiting time in ms (default = 20 ms).
Enter timeout in ms (default = 400ms).
Stop bit is fixed and not editable (default = 1 at
Parity= None).
Select Odd, Even, or None (default = None).
Enter number of retries (default = 3)
3 - 34