Honeywell CIU 888 Configuration Manual page 131

Hide thumbs Also See for CIU 888:
Table of Contents

Advertisement

Part No.: 4417584_Rev12
Getting Started
Parameters
Communication fail delay
Data fail delay
OPC UA server enable
Server URL
Refer to the parameters and configuration options in LAN tab under
LAN A port given in section 3.2.10.1 for more information.
3. Click the Secondary LAN Port tab to view the Property.
You can view or edit this property.
Parameter
Secondary IP Address
Configuration Manual
CIU 888
Configuration options
When a field communication fail occurs it is possible to
maintain last valid scan data in the CIU 888 database
during a configurable amount of time.
Minimum time to mask a field communication fail: 0 sec
(delay mechanism disabled).
Maximum time to mask a
When a field data fail occurs it is possible to maintain
last valid scan data in the CIU 888 database during a
configurable amount of time.
Minimum time to mask a field data fail: 0 sec (delay
mechanism disabled).
Maximum time to mask a field data fail:
This setting would enable / disable the OPC UA Server
on the CIU 888's ethernet port (LAN).
0 - OPC UA server is disabled
1 - OPC UA server is enabled
This setting depicts the server URL. The OPC UA cli-
ents to CIU 888 using this URL. The URL shall be in the
below format.
opc.tcp://192.168.20.10:51000
Default value: Empty string
Configuration option
In case of redundant CIUs, this indicates the IP address
of the corresponding Ethernet port in the partner CIU.
Format: w.x.y.z
Example: 10.70.100.102
3 - 101