Valid Register Ranges; Modbus Map - Honeywell CIU 888 Configuration Manual

Hide thumbs Also See for CIU 888:
Table of Contents

Advertisement

Part No.: 4417584_Rev12
Appendix H - Creation of new Modbus field device / TRL/2 Field Device
XML Tag
<DeviceInformation>
<DeviceUnits>
<Unit>
<UnitDetail>
<UnitName>
<DeviceInformation>
<DeviceUnits>
<Unit>
<UnitDetail>
<Resolution>
H.15 Valid Register Ranges
The following table indicates the valid consecutive Modbus register
address ranges in the device.
XML Tag
<ValidRegisterRanges>
<Range>
<StartRegisterAddress>
<ValidRegisterRanges>
<Range>
<EndRegisterAddress>
H.16 Modbus Map
The following table indicates the Modbus register map of the device that
can be scanned by CIU.
XML Tag
<DeviceInformation>
<ModbusMap>
<Name>
Configuration Manual
CIU 888
Description
This specifies the device
engineering unit. Refer to
section H.19 for the supported
units.
This specifies the device
engineering unit's resolution.
Description
This indicates the Modbus
Start address
This indicates the Modbus End
address
Description
This indicates the name of
the parameter in the Modbus
field device which needs to
be scanned by CIU.
Possible Values
For LEVEL : m, cm,
mm, ft, yard, in, in/16,
fis, fii/256, in/256,
1/10 mm (TRL/2)
For TEMPERATURE :
°C, °F, K, Tenth
Fahrenheit (TRL/2),
Tenth Celsius (TRL/2)
For DENSITY : kg/m³,
°API, lb/ft³, RD60, lb/
US gal, kg/l, gr/ml
For PRESSURE : kgf/
cm², Pa, kPa, psi, atm,
bar, psi_r100,
psi_r1000, mBarG
(TRL/2), mBarA (TRL/
2), 1/100 psiG (TRL/
2), 1/100 psiA (TRL/2)
-127 to 128
Possible Values
300001 to 365535
400001 to 465535
300001 to 365535
400001 to 465535
Possible Values
Any String
H - 42