Configuring A Tank - Honeywell CIU 888 Configuration Manual

Hide thumbs Also See for CIU 888:
Table of Contents

Advertisement

NOTE 8: "Time out" parameter needs to be configured based on the wireless network
NOTE: Procedure to configure FTEB and Office LAN will be same as that of FTEA
Part No.: 4417584_Rev12
Getting Started
- re-initialization of a gauge.
- 802/811 digitizer failure.
topology.
It is recommended to configure 1500ms as "Time out" value when there are 6
hops wireless network.
mentioned above.

3.2.7 Configuring a Tank

3.2.7.1 Configuring tank under serial field port
1. After Field port is configured, you need to link the Tanks to the Field
port.
2. On the Field Port 1 node, right-click and choose Add > Tank.
3. The Add Site Element window appears.
4. In the Name box, type the name of the Tank and click OK.
5. The Tank1 node is created and displayed under Field port 1.
6. By default, the Tank tab appears.
You can view or edit these properties:
Properties
Tank name
Tank available
Tank Scan
Level type
Configuration Manual
CIU 888
Description
Name of the Tank
Check, if allowed
Select Enable or Disable
Select Innage or Ullage/Outage
3 - 37