Honeywell CIU 888 Configuration Manual page 235

Hide thumbs Also See for CIU 888:
Table of Contents

Advertisement

Part No.: 4417584_Rev12
Appendix H - Creation of new Modbus field device / TRL/2 Field Device
parameter value is not possible. For example, Product level value in
device can be directly mapped to CIU Product level value but Gauge
status / Gauge alarms from the device might not directly map to CIU
Gauge status / Gauge alarms and needs a custom value map. Refer to
the following table for more information.
XML Tag
<CustomValueMap>
<CustomValue>
<DeviceParameterName>
<CustomValueMap>
<CustomValue>
<CIUMapDetail>
<Name>
<CustomValueMap>
<CustomValue>
<CIUMapDetail>
<ValueMapType>
<CustomValueMap>
<CustomValue>
<CIUMapDetail>
<DefaultValue>
<CustomValueMap>
<CustomValue>
<CIUMapDetail>
<DeviceParameterStartBitIndex>
<CustomValueMap>
<CustomValue>
<CIUMapDetail>
<DeviceParameterEndBitIndex>
Configuration Manual
CIU 888
Description
This is the device parameter
name as defined in the
Manufacturer's product data
sheet to which we need to
associate the custom value.
This indicates the CIU
Parameter Name to which
device parameter is mapped.
This indicates the value map
type.
Device parameter's
enumeration to CIU
parameter's enumeration shall
be specified here.
Default Value indicates what
should be the CIU value if
EnumerationToEnumeration is
selected for ValueMapType
and no mapping defined for a
particular device parameter
value
This value indicates the
portion of the device value
which needs to be copied to
the CIU parameter.
For example, if Bits 15 to 8 of
the device parameter needs to
be copied then BitM = 8 and
BitN = 15.
If the entire device value
needs to be copied then this
tag shall be empty
Possible Values
Any value defined as
part of
<DeviceInformation><
ModbusMap>
<Name> (or)
<DeviceInformation><
ModbusMap>
<Status><Name>
ProductLevelStatus
ProductTempStatus
WaterMeasuredStatus
DObsHIMSStatus
VapRoomTempStatus
VapRoomPressStatus
AmbientTemperature
Status
GaugeStatus
GaugeLevelAlarms
ExternalContacts
EnumerationToEnume
ration
Any value as per CIU
parameter
Any value as per
Modbus field device
Modbus datasheet
H - 49