Chapter 2
Alarm Troubleshooting
The BKUPMEMP alarm can also cause the
by BKUPMEMP, complete the following procedure to clear the BKUPMEMP and the EQPT alarm.
Caution
A software update on a standby TCC2/TCC2P can take up to 30 minutes.
Clear the BKUPMEMP Alarm
Verify that both TCC2/TCC2Ps are powered and enabled by confirming lighted ACT/SBY LEDs on the
Step 1
TCC2/TCC2Ps.
Determine whether the active or standbyTCC2/TCC2P has the alarm.
Step 2
If both TCC2/TCC2Ps are powered and enabled, reset the TCC2/TCC2P where the alarm is raised. If the
Step 3
card is the active TCC2/TCC2P, complete the
Standby Card" procedure on page
a.
b.
c.
d.
If the TCC2/TCC2P you reset does not reboot successfully, or the alarm has not cleared, call Cisco TAC
Step 4
1 800 553-2447. If the Cisco TAC technician tells you to reseat the card, complete the
Reinsert (Reseat) the Standby TCC2/TCC2P Card" procedure on page
technician tells you to remove the card and reinstall a new one, follow the
Card" procedure on page
2.7.47 BLSROSYNC
The BLSR Out Of Synchronization alarm occurs is raised temporarily during a span upgrade,
downgrade, or two-fiber to four-fiber mode upgrade and clears when the procedure is complete for all
nodes on the ring. If the alarm does not clear, ensure that all maintenance procedures have completed for
all nodes on the ring. If the alarm still does not clear, log into the Technical Support Website at
http://www.cisco.com/techsupport for more information or call Cisco TAC 1 800 553-2447 in order to
report a Service-Affecting (SA) problem.
2.7.48 BLSR-SW-VER-MISM
November 2009
Problem at the driver level.
Code volume fails cyclic redundancy checking (CRC, a method to verify for errors in data
transmitted to the TCC2/TCC2P).
Right-click the standby TCC2/TCC2P in CTC.
Choose Reset Card from the shortcut menu.
Click Yes in the Are You Sure dialog box. The card resets, the FAIL LED blinks on the physical card.
Wait ten minutes to verify that the card you reset completely reboots.
2-273.
Default Severity: Major (MJ), Service-Affecting (SA)
SONET Logical Object: OCN
Default Severity: Major (MJ), Service-Affecting (SA)
SONET Logical Object: OCN
"EQPT" alarm on page
"Reset an Active TCC2/TCC2P Card and Activate the
2-270. If the card is the standby TCC2/TCC2P:
Cisco ONS 15454 Troubleshooting Guide, R8.5
2.7.47 BLSROSYNC
2-85. If the EQPT alarm is caused
"Remove and
2-272. If the Cisco TAC
"Physically Replace a Traffic
2-57