2.7.43 BAT-FAIL
2.7.43 BAT-FAIL
The Battery Fail alarm occurs when one of the two power supplies (A or B) is not detected. This could
be because the supply is removed or is not operational. The alarm does not distinguish between the
individual power supplies, so onsite information about the conditions is necessary for troubleshooting.
Clear the BAT-FAIL Alarm
At the site, determine which battery is not present or operational.
Step 1
Remove the power cable from the faulty supply. For procedures, refer to the "Install the Shelf and
Step 2
Backplane Cable" chapter in the Cisco ONS 15454 Procedure Guide. Reverse the power cable
installation procedure.
If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
Step 3
for more information or call Cisco TAC 1 800 553-2447 in order to report a Service-Affecting (SA)
problem.
2.7.44 BERT-ENBL
Default Severity: Not Reported (NR), Non-Service-Affecting (NSA)
SONET Logical Object: DS1/DS3
The Bert Enabled alarm specifies that the bit error rate testing (BERT) feature is enabled.
2.7.45 BERT-SYNC-FAIL
Default Severity: Not Reported (NR), Non-Service-Affecting (NSA)
SONET Logical Object: DS1/DS3
The Bert Synchronization Fail alarm occurs when the errors injected by the Test Pattern Generator (TPG)
reaches the Test Pattern Monitor (TPM) and connectivity fails. This alarm clears when TPG and TPM
synchronize.
2.7.46 BKUPMEMP
The Primary Nonvolatile Backup Memory Failure alarm refers to a problem with the TCC2/TCC2P flash
memory. The alarm occurs when the TCC2/TCC2P is in use and has one of four problems:
Cisco ONS 15454 Troubleshooting Guide, R8.5
2-56
Default Severity: Major (MJ), Service-Affecting (SA)
SONET Logical Object: PWR
Default Severity: Critical (CR), Service-Affecting (SA)
SONET Logical Object: EQPT
Flash manager fails to format a flash partition.
Flash manager fails to write a file to a flash partition.