MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)

3.5.5 Meter logical device

The Ctrl logical device contains logical nodes that model UR metering and measurement functions (other than PMU),
including Signal Sources.
The Meter logical device is available when the Advanced IEC 61850 option is purchased with the UR device.
3.5.5.1 Logical node zero (LLN0)
LLN0 is instantiated in all UR family devices implementing the Meter logical device.
Table 3-194: LLN0 data objects
LNName: LLN0
data obj. data attribute
Beh
3
stVal
stVal
Health
stVal
On
stVal
Off
stVal
Zero
mag
mag.f
Mod
ctlVal
stVal
ctlModel
sboTimeout
sboClass
operTimeout
GrRef
setSrcRef
MltLev
setVal
<TTΣDataS
et##>
DSMemberRef[η] ObjectReference
3.5.5.2 AC signal sources (ACsrc)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
3-168
LDevice inst: Meter
UR element: Nameplate information for the logical nodes
Type
FC UR Name
ENS
ENUMERATED
ST
ENUMERATED
ST
LLN0.Beh.stVal of the Master
logical device
ENS
ENUMERATED
ST
LPHD1.PhyHealth.stVal
SPS
BOOLEAN
ST
SPS
BOOLEAN
ST
MV
AnalogueValue
MX
FLOAT32
ENC
ENUMERATED
ENUMERATED
ST
CtlModels
CF
LLN0.Mod.ctlModel
INT32U
CF
SboClasses
CF
INT32U
CF
ORG
ObjectReference SP
For communications, mapped to
Master ldName if not empty,
otherwise to the concatenation
of the IED name and "Master".
For SCL, mapped to the
concatenation of the IED name
and "Master".
SPG
BOOLEAN
SP
DATA-SET
DataSet Member η
CHAPTER 3: IEC 61850 COMMUNICATION
Description
This logical device's behavior
Only instantiated in the Master logical
device
Only instantiated in the Master logical
device
Only instantiated in the Master logical
device
Only instantiated in the Master logical
device
0.0
Only instantiated in the Master logical
device
2, the code for SBO control with normal
security according to IEC 61850-7-2.
30000
0 (operate-once)
0
Reference to root logical device
reference to the data attribute to input
Instantiated only in the Master logical
device
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R/Ctrl
R
R
R/C
R
R
R
R
R
R
R
R
R/C