GE B30 Communications Manual page 423

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: EnrMtrMMTR#
data obj. data attribute
Type
NegTotWh
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
PosTotVArh
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
NegTotVAr
MV
h
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
RsStat
SPC
pulseConfig
PulseConfig
pulseConfig
ENUMERATED
.cmdQual
pulseConfig.onDur INT32U
pulseConfig
INT32U
.offDur
pulseConfig
INT32U
.numPls
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
InRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Meter
UR element: Signal Source # Energy Metering
FC UR Name
MX
SRC # NEG WATTHOUR
MX
CF
CF
EnrMtrMMTR#.NegTotWh.db
MX
SRC # T POS VARHOUR
MX
CF
CF
EnrMtrMMTR#.PosTotVArh.db
MX
SRC # NEG VARHOUR
MX
CF
CF
EnrMtrMMTR#.NegTotVArh.db
CF
CF
EnrMtrMMTR1.RsStat.ctlModel
CF
CF
CF
setting reference to clear
Energy, which shows the
receiving of dynamically clearing
signal for energy calculation
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
SRC # Total Watt-hour in negative
direction
instMag.f deadbanded
72, the code for real energy in watt hours
(Wh)
0, the code for a multiplier of 1
SRC # Total VAr-hour in positive direction R
instMag.f deadbanded
73, the code for reactive energy in volt
ampere hours (VArh)
0, the code for a multiplier of 1
SRC # Total VAr-hour in negative directionR
instMag.f deadbanded
73, the code for reactive energy in volt
ampere hours (VArh)
0, the code for a multiplier of 1
only instantiated in EnrMtrMMTR1
0 (pulse)
0 indicates the duration is locally defined R
0
1
1, the code for direct control with normal
security; 2 is code for SBO with normal
security.
30000
0 (operate-once)
0
CLEAR ENERGY setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
R/W/C
R
R
R
R
R
R
R
R
R/W/C
3
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R/W/C
R/Ctrl
R
R
R
R
R/W/C
R
R
R
R
R/C
R/C
3-185