GE B30 Communications Manual page 101

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
6151
Transformer Aging Factor Pickup
"
6152
Transformer Aging Factor Delay
"
6153
Transformer Aging Factor Block
"
6155
Transformer Aging Factor Target
"
6156
Transformer Aging Factor Events
Transformer Loss of Life (Read/Write Grouped Setting)
G30, T35, T60
6160
Transformer Loss of Life Function
"
6161
XFMR LOL Initial Value
"
6163
Transformer Loss of Life Pickup
"
6165
Transformer Loss Of Life Block
"
6167
Transformer Loss of Life Target
"
6168
Transformer Loss of Life Events
Transformer Thermal Inputs (Read/Write Setting)
G30, T35, T60
6170
Transformer Thermal Model Source Input
"
6171
Ambient Temperature Input Sensor
"
6172
Top Oil Temperature Input Sensor
"
6173
January Average Ambient Temperature
"
6174
February Average Ambient Temperature
"
6175
March Average Ambient Temperature
"
6176
April Average Ambient Temperature
"
6177
May Average Ambient Temperature
"
6178
June Average Ambient Temperature
"
6179
July Average Ambient Temperature
"
617A
August Average Ambient Temperature
"
617B
September Average Ambient Temperature -60 to 60
"
617C
October Average Ambient Temperature
"
617D
November Average Ambient Temperature
"
617E
December Average Ambient Temperature
Transformer Thermal Inputs (Read/Write Command)
G30, T35, T60
6180
Transformer Loss of Life Clear Command
Transformer Percent Differential (Read/Write Grouped Setting)
G30, T35, T60
61C0
Percent Differential Function
"
61C1
Percent Differential Pickup
"
61C2
Percent Differential Slope 1
"
61C3
Percent Differential Break 1
"
61C4
Percent Differential Break 2
"
61C5
Percent Differential Slope 2
"
61C6
Inrush Inhibit Function
"
61C7
Inrush Inhibit Level
"
61C8
Overexcitation Inhibit Function
"
61C9
Overexcitation Inhibit Level
"
61CA
Percent Differential Block
"
61CC
Percent Differential Target
"
61CD
Percent Differential Events
"
61CE
Transformer Inrush Inhibit Mode
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
1 to 10
PU
0.1
0 to 30000
min
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 500000
hrs
1
0 to 500000
hrs
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 5
---
1
0 to 32
---
1
0 to 32
---
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
0 to 1
---
1
0 to 1
---
1
0.05 to 1
pu
0.001 F001
15 to 100
%
1
1 to 2
pu
0.001 F001
2 to 30
pu
0.001 F001
50 to 100
%
1
0 to 2
---
1
1 to 40
%f
0.1
o
0 to 1
---
1
1 to 40
%f
0.1
o
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 3
---
1
MEMORY MAP
Format
Default
F001
20
F001
10
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F003
0
F003
180000
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F167
0 (SRC 1)
F450
0
F460
0
F002
-20
F002
-30
F002
-10
F002
10
F002
20
F002
30
F002
30
F002
30
F002
20
F002
10
F002
10
F002
-10
F126
0 (No)
F102
0 (Disabled)
100
F001
25
2000
8000
F001
90
F168
1 (Adapt.
2nd)
F001
200
F169
0 (Disabled)
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F189
0 (Per phase)
2-81
2