CHAPTER 3: IEC 61850 COMMUNICATION
LNName: LinDfPDIF1
data obj. data attribute
Type
CrcFailζ
SPS
stVal
BOOLEAN
IdFailζ
SPS
stVal
BOOLEAN
AnyGpsFail
SPS
stVal
BOOLEAN
MaxAsymO
SPS
stVal
BOOLEAN
TmChgOpζ
SPS
stVal
BOOLEAN
GpsFailζ
SPS
stVal
BOOLEAN
Blk
SPS
stVal
BOOLEAN
BlkHφ
SPS
stVal
BOOLEAN
DistDet
SPS
stVal
BOOLEAN
StubBusOp
SPS
stVal
BOOLEAN
DifAClc
WYE
phsθ
CMV
phsθ.instCVal
Vector
phsθ.instCVal.mag
FLOAT32
.f
phsθ.instCVal.ang
FLOAT32
.f
phsθ.cVal
Vector
phsθ.cVal.mag.f
FLOAT32
phsθ.cVal.ang.f
FLOAT32
phsθ.units
Unit
phsθ.units.SIUnit ENUMERATED
phsθ.units
ENUMERATED
.multiplier
phsθ.db
INT32U
phsθ.dbAng
INT32U
phsθ.zeroDb
INT32U
neut
CMV
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Line Differential element (ANSI 87L) phase and general
functions
FC UR Name
ST
87L DIFF CHζ CRCFAIL
ST
87L DIFF CHζ ID FAIL
ST
87L DIFF GPS FAIL
ST
87L DIFF CHζ MAX ASYM
ST
87L DIFF CHζ TIME CHNG
ST
87L DIFF GPS ζ FAIL
ST
87L DIFF BLOCKED
ST
87L HARM2 θ OP
ST
50DD SV
ST
STUB BUS OP
MX
Iθ DIFF. CURRENT magnitude, in
primary amps
Iθ DIFF. CU
MX
Iθ DIFF. CURRENT magnitude, in
primary amps, with deadband
Iθ DIFF. CU
CF
CF
LinDfPDIF1.DifAClc.phsθ.db
CF
LinDfPDIF1.DifAClc.phsθ.dbAng
CF
CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
87L DIFF CHζ CRCFAIL operand, which
becomes on when the differential
element's has detected the CRC error
threshold has been exceeded on channel
ζ.
87L DIFF CHζ ID FAIL operand, which
becomes on when the differential
element's ID check for a peer L90 on
channel ζ has failed.
87L DIFF GPS FAIL operand, which
becomes on when the GPS signal failed
or is not configured properly at any
terminal.
87L DIFF CHζ MAX ASYM operand, which
becomes on when the Asymmetry on
channel ζ exceeded preset value.
87L DIFF CHζ TIME CHNG operand, which
becomes on when the Change in round
trip delay on channel ζ exceeded preset
value.
87L DIFF GPS ζ FAIL operand.
87L DIFF BLOCKED operand, which
becomes On when the 87L function is
blocked due to communication problems.
only instantiated in L90
50DD SV operand, which becomes On
when the 87L disturbance detector has
operated.
STUB BUS OP operand, which becomes
On when the Stub Bus function is active.
Differential currents
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
5, the code for amps
0, the code for a multiplier of 1
R/W/C
R
R
R
R
R
3
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
3-63