MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: BkrFaRBRF#
data obj. data attribute
setSrcRef
setSrcCB
InRefγ05
setSrcRef
setSrcCB
InRefγ06
setSrcRef
setSrcCB
InRefγ07
setSrcRef
3
setSrcCB
InRefγ08
setSrcRef
setSrcCB
OpIn
general
phsA
phsB
phsC
BkrOp&
stVal
OpEx
general
InRefγ09
setSrcRef
setSrcCB
InRefγ10
setSrcRef
setSrcCB
InRefγ11
setSrcRef
setSrcCB
3.5.2.12 Breaker flashover (FlshOv)
This element is instantiated in the following products: B30, C60, C70, D60, F35, F60, G60, L60, L90, M60, T60.
Table 3-31: Breaker flashover data objects
LNName: FlshOvPIOC#
data obj. data attribute
Op
general
phsA
phsB
phsC
Str
3-44
LDevice inst: Prot
UR element: Breaker Control element #
Type
FC UR Name
ObjectReference SP
BF# BKR POS2 φA/3P.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS1 φB.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS1 0C.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS2 φB.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS2 φC.
ObjectReference SP
ACT
BOOLEAN
ST
re-trip operand BKR FAIL #
RETRIP
BOOLEAN
ST
re-trip operand BKR FAIL #
RETRIPA
BOOLEAN
ST
re-trip operand BKR FAIL #
RETRIPB
BOOLEAN
ST
re-trip operand BKR FAIL #
RETRIPC
SPS
BOOLEAN
ST
BKR FAIL # T& OP
ACT
BOOLEAN
ST
trip operand BKR FAIL # TRIP OP
ORG
ObjectReference SP
BF# PH A INITIATE.
ObjectReference SP
ORG
ObjectReference SP
BF# PH B INITIATE.
ObjectReference SP
ORG
ObjectReference SP
BF# PH C INITIATE.
ObjectReference SP
LDevice inst: Prot
UR element: BREAKER FLASHOVER element #
Type
FC UR Name
ACT
BOOLEAN
ST
BKR # FLSHOVR OP
BOOLEAN
ST
BKR # FLSHOVR OP A
BOOLEAN
ST
BKR # FLSHOVR OP B
BOOLEAN
ST
BKR # FLSHOVR OP C
ACD
CHAPTER 3: IEC 61850 COMMUNICATION
Description
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS1 φB setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS1 φC setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS2 φB setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS2 φC setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BKR FAIL # RETRIP operands
BKR FAIL # T& OP operand
BKR FAIL # TRIP OP operand
BF# PH A INITIATE setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# PH B INITIATE setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# PH C INITIATE setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
BKR # FLSHOVR OP operand (including
individual three phases)
BKR # FLSHOVR PKP operand (including
individual three phases)
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R
R

Advertisement