CHAPTER 3: IEC 61850 COMMUNICATION
13130
lnInst="1" doName="Op" daName="general" fc="ST"/>
13131
13132
buffered="true" bufTime="0" indexed="false">
13133
period="true" gi="true"/>
13134
reasonCode="true" dataRef="true" bufOvfl="false" entryID="false" configRef="true"/>
13135
13136
Following is the element for a typical data object that is mapped to a FlexLogic operand. The Val element on line 47166
was within the TEMPLATE IED element, in the Prot LDevice element, and in the LN element with lnClass="PIOC" inst="1"
prefix="PhsIoc", so the text in the Val element is the configured value of data attribute TEMPLATEProt/PhsIocPIOC1.Dpo.d.
47164
47165
47166
47167
47168
Following is the element for a typical data object that is mapped to a setting that selects a FlexLogic operand. The Val
element on line 47186 was within the same LN element shown previously, so the text of the Val element is the configured
value of TEMPLATEProt/PhsIocPIOC1.BlkRef11.setSrcRef, which has here a 61850 ObjectReference to the FlexLogic
operand "Off." The "@" represents the name of the containing IED element.
47184
47185
47186
47187
47188
47189
47190
47191
47192
group 1.</Val>
47193
47194
The IED element describes the structure of the information model by specifying for each logical node its lnType (for
example, see line 13127 earlier). After the IED element, there is a DataTypeTemplates element that contains LNodeType
elements that define for each lnType the data objects contained in logical nodes of that lnType. Similarly, the components
of each data object type are defined in DOType elements, and the components of structured data attributes are defined in
DAType elements.
3.1.8.3 Deadbands
Deadbands for measured values
The "db" data attributes are used by the relay to determine when to update the "mag" and "cVal" values from the
associated "instmag" and "instcVal" values. Updates trigger reports and GOOSE messages.
UR FAMILY – COMMUNICATIONS GUIDE
<FCDA ldInst="Prot" prefix="PhsIoc" lnClass="PIOC"
</DataSet>
<ReportControl name="BRCB01"
<TrgOps dchg="true" qchg="true" dupd="false"
<OptFields seqNum="true" timeStamp="true" dataSet="true"
<RptEnabled max="1"/>
</ReportControl>
<DOI name="Dpo">
<DAI name="d">
<Val>PHASE IOC1 DPO operand</Val>
</DAI>
</DOI>
<DOI name="BlkRef11">
<DAI name="setSrcRef">
<Val>@Master/LLN0.Off.stVal</Val>
</DAI>
<DAI name="setSrcCB">
<Val></Val>
</DAI>
<DAI name="d">
<Val>PHASE IOC1 BLOCK A setting for setting
</DAI>
</DOI>
OVERVIEW
intgPd="0" confRev="1"
3
3-17