MEMORY MAP
Products
Address Register name
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (12 Modules)
All except B90,
5A00
C30
"
5A01
"
5A02
2
"
5A03
"
5A04
"
5A05
"
5A0B
"
5A0C
"
5A0D
"
5A13
"
5A26
"
5A39
"
5A4C
"
5A5F
"
5A72
"
5A85
"
5A98
"
5AAB
"
5ABE
"
5AD1
Neutral Time Overcurrent (Read/Write Grouped Setting) (2 or 6 Modules)
B30, C60, C70,
5B00
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
M60, N60, T60
"
5B01
"
5B02
"
5B03
"
5B04
"
5B05
"
5B06
"
5B07
"
5B09
"
5B0A
"
5B0B
2-72
Phase Instantaneous Overcurrent 1
Function
Phase Instantaneous Overcurrent 1 Signal
Source
Phase Instantaneous Overcurrent 1 Pickup 0.005 to 30
Phase Instantaneous Overcurrent 1 Delay
Phase Instantaneous Overcurrent 1 Reset
Delay
Phase IOC1 Block For Each Phase (3 items) 0 to 4294967295
Phase Instantaneous Overcurrent 1 Target 0 to 2
Phase Instantaneous Overcurrent 1 Events 0 to 1
Reserved (6 items)
...Repeated for Phase Instantaneous
Overcurrent 2
...Repeated for Phase Instantaneous
Overcurrent 3
...Repeated for Phase Instantaneous
Overcurrent 4
...Repeated for Phase Instantaneous
Overcurrent 5
...Repeated for Phase Instantaneous
Overcurrent 6
...Repeated for Phase Instantaneous
Overcurrent 7
...Repeated for Phase Instantaneous
Overcurrent 8
...Repeated for Phase Instantaneous
Overcurrent 9
...Repeated for Phase Instantaneous
Overcurrent 10
...Repeated for Phase Instantaneous
Overcurrent 11
...Repeated for Phase Instantaneous
Overcurrent 12
Neutral Time Overcurrent 1 Function
Neutral Time Overcurrent 1 Signal Source
Neutral Time Overcurrent 1 Input
Neutral Time Overcurrent 1 Pickup
Neutral Time Overcurrent 1 Curve
Neutral Time Overcurrent 1 Multiplier
Neutral Time Overcurrent 1 Reset
Neutral Time Overcurrent 1 Block
Neutral Time Overcurrent 1 Target
Neutral Time Overcurrent 1 Events
Reserved (6 items)
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
0 to 1
---
1
0 to 5
---
1
pu
0.001 F001
0 to 600
s
0.01
0 to 600
s
0.01
---
1
---
1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 1
---
1
0.02 to 30
pu
0.001 F001
0 to 16
---
1
0 to 600
---
0.01
0 to 1
---
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
UR FAMILY – COMMUNICATIONS GUIDE
Format
Default
F102
0 (Disabled)
F167
0 (SRC 1)
1000
F001
0
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F122
0 (Phasor)
1000
F103
0 (IEEE Mod
Inv)
F001
100
F104
0
(Instantaneo
us)
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0