GE B30 Communications Manual page 431

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: DatLogRDRE1
data obj. data attribute
Type
stVal
BOOLEAN
MemClr
SPC
pulseConfig
PulseConfig
pulseConfig
ENUMERATED
.cmdQual
pulseConfig.onDur INT32U
pulseConfig
INT32U
.offDur
pulseConfig
INT32U
.numPls
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
InRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.6.7 Digital counters (DigCnt)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-210: Digital counter data objects
LNName: DigCntFCNT#
data obj. data attribute
Type
HiLim
SPS
stVal
BOOLEAN
EqLim
SPS
stVal
BOOLEAN
LoLim
SPS
stVal
BOOLEAN
CntVal
BCR
actVal
INT64
frVal
INT64
frTm
TimeStamp
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
pulsQty
FLOAT32
frEna
BOOLEAN
strTm
TimeStamp
frPd
INT32
frRs
BOOLEAN
InRef1
ORG
setSrcRef
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Gen
UR element: Data Logger
FC UR Name
ST
Transitions to true whenever a
new sample is recorded, cleared
to false when recorder is
cleared.
CF
CF
DatLogRDRE1.MemClr.ctlModel
CF
CF
CF
DATA LOGGER TRIGGER setting reference to the data attribute to input
LDevice inst: Gen
UR element: Digital Counters #
FC UR Name
ST
Counter #(CNT#) HI
ST
Counter #(CNT#) EQL
ST
Counter #(CNT#) LO
ST
actual value of Counter #
ACCUM
ST
actual value of Counter #
FROZEN (count)
ST
actual value of Counter #
FROZEN (date/time) combined
with Counter # MICROS
(fractional seconds)
COUNTER # UNITS
COUNTER # UNITS
CF
CF
CF
CF
CF
COUNTER # UP setting
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Clear all data logger records command R/Ctrl
0 (pulse)
2 ms (actually one pass)
0
1
30000
0 (operate-once)
0
DATA LOGGER TRIGGER setting.
source GoCB of input if via GOOSE
Description
Counter #(CNT#) HI, which indicates the
number of pulses counted is above the
set number.
Counter #(CNT#) EQL operand, which
indicates the number of pulses counted is
equal to the set number
Counter #(CNT#) LO operand, which
indicates the number of pulses counted is
below the set number.
Counter # ACCUM, which indicates the
accumulated number of pulses
1
0
0
COUNTER # UP setting.
reference to the data attribute to input
R/W/C
R
R
R
R
R
R
R/W/C
3
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
3-193