GE B30 Communications Manual page 230

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MEMORY MAP
F502
BITFIELD: ELEMENT OPERATE STATES
Each bit contains the operate state for an element. See the F124
format code for a list of element IDs. The operate bit for element
ID X is bit [X mod 16] in register [X/16].
2
F513
ENUMERATION: POWER SWING MODE
0 = Two Step, 1 = Three Step
F514
ENUMERATION: POWER SWING TRIP MODE
0 = Delayed, 1 = Early
F515
ENUMERATION ELEMENT INPUT MODE
0 = SIGNED, 1 = ABSOLUTE
F516
ENUMERATION ELEMENT COMPARE MODE
0 = LEVEL, 1 = DELTA
F517
ENUMERATION: ELEMENT DIRECTION OPERATION
0 = OVER, 1 = UNDER
F518
ENUMERATION: FLEXELEMENT UNITS
0 = Milliseconds, 1 = Seconds, 2 = Minutes
F519
ENUMERATION: NON-VOLATILE LATCH
0 = Reset-Dominant, 1 = Set-Dominant
F521
ENUMERATION: GROUND DISTANCE POLARIZING CURRENT
0 = Zero-Sequence, 1 = Negative-Sequence
F522
ENUMERATION: TRANSDUCER DCmA OUTPUT RANGE
0 = –1 to 1 mA, 1 = 0 to 1 mA, 2 = 4 to 20 mA
2-210
CHAPTER 2: MODBUS COMMUNICATION
F523
ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT
VARIATION
Bitmask
Default variation
0
1
1
2
2
5
3
6
F524
ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION
Bitmask
Default variation
0
1
1
2
2
9
3
10
F525
ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION
Bitmask
Default variation
0
1
1
2
2
3
3
4
4
5
5
7
F530
ENUMERATION: FRONT PANEL INTERFACE KEYPRESS
Value Keypress
Value Keypress
0
None
15
3
1
Menu
16
Enter
2
Message Up
17
Message
Down
3
7
~ 18
0
4
8
19
Decimal
5
9
20
+/–
6
Help
21
Value Up
7
Message
22
Value Down
Left
8
4
23
Reset
9
5
24
User 1
10
6
25
User 2
11
Escape
26
User 3
12
Message
31
User PB 1
Right
UR FAMILY – COMMUNICATIONS GUIDE
Value Keypress
33
User PB 3
34
User PB 4
35
User PB 5
~ 36
User PB 6
37
User PB 7
38
User PB 8
39
User PB 9
40
User PB 10
41
User PB 11
42
User PB 12
44
User 4
45
User 5
46
User 6