MEMORY MAP
F259
ENUMERATION: BRICK RTD TYPE
0 = 100 Ohm Nickel, 1 = 120 Ohm Nickel, 2 = 100 Ohm Platinum
F260
ENUMERATION: DATA LOGGER MODE
2
0 = Continuous, 1 = Trigger
F261
ENUMERATION: BANK REDUNDANCY TYPE
0 = None, 1 = Dependability Biased, 2 = Security Biased
F262
ENUMERATION: BRICK STATUS
0 = Disabled, 1 = OK, 2 = Communications Trouble, 3 = Equipment
Mismatch, 4 = Brick Trouble
F270
ENUMERATION: FAULT REPORT VT SUBSTITUTION
Value
Description
0
None
1
I0
2
V0
F280
ENUMERATION: BREAKER/SWITCH NV LATCH PACKED
STATES BIT POSITIONS
Value
Description
0
Tagged Bit
1
Subd Closed Bit
2
Subd Open Bit
3
Bypassed Bit
4
Blk Rcls Bit
F281
ENUMERATION: BREAKER/SWITCH PACKED STATES BIT POSI-
TIONS
Value
Description
0
Closed Bit
1
Open Bit
2
Discrep Bit
3
Ph A Interm Bit
4
Ph B Interm Bit
5
Ph C Interm Bit
6
Bad Status Bit
2-208
CHAPTER 2: MODBUS COMMUNICATION
Value
Description
7
OOS Bit
8
Tagged Bit
9
Subd Clsd Bit
10
Subd Open Bit
11
Bypassed Bit
12
Blk Rcls Bit
13
Ar Armed Bit
14
Racked In Bit
15
Trouble Bit
F282
ENUMERATION: BREAKER/SWITCH COMMAND
Value
Description
0
Cancel
1
Open
2
Close
3
Tag
4
Untag
5
Substitute Closed
6
Substitute Open
7
Remove Substitution
8
Bypass
9
Remove Bypass
10
Block Autoreclose
11
Unblock Autoreclose
F300
UR_UINT32: FLEXLOGIC BASE TYPE (15-bit type)
The FlexLogic BASE type is 14 bits and is combined with a 17-bit
descriptor and 1 bit for the protection element to form a 32-bit
value. The combined bits are of the form:
PTTTTTTTTTTTTTTDDDDDDDDDDDDDDDDD, where P bit if set
indicates that the FlexLogic type is associated with a protection
element state and D represents bits for the type in F124 format. If
P bit is not set, then the T represents bits for the type and D repre-
sents range.
The values in square brackets indicate the base type with P prefix
[PTTTTTTTTTTTTTT] and the values in round brackets indicate the
descriptor range. The left-most D bit indicates whether the type is
an ON or OFF type. There can be a total 65535 BASE type ele-
ments, 131071 protection element IDs, and 16383 element states.
There can be a total of 65535 descriptors of each type.
[0] Off (0) – This is boolean FALSE value
[1] On (1) – This is boolean TRUE value
[2] CONTACT INPUTS (1 to 120)
[3] CONTACT INPUTS OFF (1 to 120)
[4] VIRTUAL INPUTS (1 to 32)
[6] VIRTUAL OUTPUTS (1 to 64)