CHAPTER 3: IEC 61850 COMMUNICATION
LNName: BusDifPDIF#
data obj. data attribute
Type
angRef
ENUMERATED
InRef2τ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.14 Capacitor bank phase overvoltage (CPhOv)
This element is instantiated in the following products: C70.
Table 3-33: C70 capacitor bank phase overvoltage function data objects
LNName: CPhOvPTOV#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
phsA
BOOLEAN
dirPhsA
ENUMERATED
phsB
BOOLEAN
dirPhsB
ENUMERATED
phsC
BOOLEAN
dirPhsC
ENUMERATED
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
OpV
WYE
phsA
CMV
phsA.instCVal
Vector
phsA.instCVal.mag
FLOAT32
.f
phsA.cVal
Vector
phsA.cVal.mag.f
FLOAT32
phsA.units
Unit
phsA.units.SIUnit ENUMERATED
phsA.units
ENUMERATED
.multiplier
phsA.db
INT32U
phsA.zeroDb
INT32U
phsB
CMV
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Bus Differential element # (ANSI 87B)
FC UR Name
CF
BUS ZONE #τ STATUS setting
BUS ZONE # DIFF BLK.
LDevice inst: Prot
UR element: BANK OVERVOLTAGE element #
FC UR Name
ST
BANK OV # PKP
ST
ST
BANK OV # PKP A
ST
ST
BANK OV # PKP B
ST
ST
BANK OV # PKP C
ST
ST
BANK OV # OP
ST
BANK OV # OP A
ST
BANK OV # OP B
ST
BANK OV # OP C
ST
BANK OV # DPO
BANK OV # BLK for group γ.
MX
Bank overvoltage # phase A
operate voltage
MX
CF
CF
CPhOvPTOV#.OpV.phsAdb
CF
(VOLTAGE CUT-OFF LEVEL) / 275 *
100 000
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
BUS ZONE #τ STATUS setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BUS ZONE # DIFF BLK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
BANK OV # PKP operands (including
individual three phases), which indicates
element will operate when delay expires.
0, the code for unknown. It is unknown as
the element is non-directional
0, the code for unknown.
0, the code for unknown.
0, the code for unknown.
BANK OV # OP operands (including
individual three phases)
BANK OV # DPO operand
BANK OV # BLK setting for setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Bank Operating Voltage in per unit for Ph
A, B, and C
instCVal.mag.f deadbanded
1, the code for dimensionless (per unit)
0, the code for a multiplier of 1
R/W/C
R
R
R/C
R/C
R
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
3-47

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents