GE B30 Communications Manual page 167

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
A029
Motor Load Deviation at Broken Rotor Bar
Maximum
"
A02A
Time Stamp at Broken Rotor Bar Maximum 0 to 4294967295
Broken Rotor Bar Commands (Read/Write Commands)
M60
A02D
Broken Rotor Bar Clear Data Command
Broken Rotor Bar Detection (Read/Write Settings)
M60
A030
Broken Rotor Bar Function
"
A031
Start of Broken Rotor Bar Offset
"
A032
End of Broken Rotor Bar Offset
"
A033
Broken Rotor Bar Start Block Delay
"
A034
Minimum Motor Load
"
A035
Maximum Load Deviation
"
A036
Maximum Current Unbalance
"
A037
Broken Rotor Bar Pickup
"
A038
Broken Rotor Bar Reset Delay
"
A039
Broken Rotor Bar Block
"
A03B
Broken Rotor Bar Target
"
A03C
Broken Rotor Bar Events
Pilot Permissive Overreach Transfer Trip (POTT) Settings (Read/Write)
L60
A070
POTT Scheme Function
"
A071
POTT Permissive Echo
"
A072
POTT Rx Pickup Delay
"
A073
POTT Transient Block Pickup Delay
"
A074
POTT Transient Block Reset Delay
"
A075
POTT Echo Duration
"
A076
POTT Line End Open Pickup Delay
"
A077
POTT Seal In Delay
"
A078
POTT Ground Direction OC Forward
"
A07A
POTT Rx
"
A07C
POTT Echo Lockout
"
A07D
POTT Target
"
A07E
POTT Events
VT Fuse Failure Settings (Read/Write) (2, 4, or 6 Modules)
C60, C70, D30,
A09A
VT Fuse Failure Function
D60, F35, F60,
G30, G60, L30,
L60, L90, M60,
N60, T60
"
A09B
VT Fuse Failure Neutral Wire Open Function 0 to 1
"
A09C
VT Fuse Failure Neutral Wire Open 3rd
Harmonic Pickup
"
A09D
VT Fuse Failure 1 Alarm Delay
"
A09E
...Repeated for Source 2
C60, C70, D60,
A0A2
...Repeated for Source 3
F35, F60, G30,
G60, L90, M60,
N60, T60
"
A0A6
...Repeated for Source 4
C70, F35, N60,
A0AA
...Repeated for Source 5
T60
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1.5
× FLA
0.01
---
1
0 to 1
---
1
0 to 1
---
1
–12 to 11.99
Hz
0.01
–11.99 to 12
Hz
0.01
0 to 600
s
0.01
0.5 to 1
× FLA
0.01
0 to 1
× FLA
0.01
0 to 100
%
0.1
–60 to –12
dB
1
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 65.535
s
0.001 F001
0 to 65.535
s
0.001 F001
0 to 65.535
s
0.001 F001
0 to 65.535
s
0.001 F001
0 to 65.535
s
0.001 F001
0 to 65.535
s
0.001 F001
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 65.535
s
0.001 F001
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
---
1
0.004 to 3
pu
0.001 F001
0 to 65.535
s
0.001 F001
MEMORY MAP
Format
Default
F001
0
F050
0
F126
0 (No)
F102
0 (Disabled)
F002
40
F002
200
F001
6000
F001
70
F001
10
F001
150
F002
-40
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
0
20
90
100
50
400
F300
0
F300
0
250
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
100
1000
2-147
2