MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: LLN0
data obj. data attribute
<TTΣDataS
et##>
DSMemberRef[η] ObjectReference
3.5.2.2 Accidental energization (AcdEnr)
This element is instantiated in the following products: G30, G60.
Table 3-20: Accidental energization data objects
LNName: AcdEnrPIOC1
data obj. data attribute
Op
general
3
Dpo
stVal
Armed
stVal
InRefγ
setSrcRef
setSrcCB
BlkRefγ
setSrcRef
setSrcCB
3.5.2.3 Auxiliary overvoltage (AuxOv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T60.
Table 3-21: Auxiliary overvoltage data objects
LNName: AuxOvPTOV#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
BlkRefγ
setSrcRef
setSrcCB
3.5.2.4 Auxiliary undervoltage (AuxUv)
This element is instantiated in the following products: C60, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T60.
Table 3-22: Auxiliary undervoltage data objects
LNName: AuxUvPTUV#
data obj. data attribute
Str
general
dirGeneral
3-38
LDevice inst: Prot
UR element: Nameplate information for the logical nodes
Type
FC UR Name
DATA-SET
DataSet Member η
LDevice inst: Prot
UR element: Accidental Energization element – Over-current function
Type
FC UR Name
ACT
BOOLEAN
ST
ACCDNT ENRG OP
SPS
BOOLEAN
ST
ACCDNT ENRG DPO
SPS
BOOLEAN
ST
ACCDNT ENRG ARMED
ORG
ObjectReference SP
ACCDNT ENRG OFFLINE
ObjectReference SP
ORG
ObjectReference SP
ACCDNT ENRG BLOCK
ObjectReference SP
LDevice inst: Prot
UR element: Auxiliary Overvoltage element # functions
Type
FC UR Name
ACD
BOOLEAN
ST
AUX OV# PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
AUX OV# OP
SPS
BOOLEAN
ST
AUX OV# DPO
ORG
ObjectReference SP
AUX OV# BLK for group γ.
ObjectReference SP
LDevice inst: Prot
UR element: Auxiliary Undervoltage element# functions
Type
FC UR Name
ACD
BOOLEAN
ST
AUX UV# PKP
ENUMERATED
ST
CHAPTER 3: IEC 61850 COMMUNICATION
Description
Description
ACCDNT ENRG OP operand
ACCDNT ENRG DPO operand
ACCDNT ENRG ARMED operand
ACCDNT ENRG OFFLINE setting for
setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
ACCDNT ENRG BLOCK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
AUX OV# PKP operands (including
individual three phases)
0, the code for unknown. It is unknown as
the element is non-directional
AUX OV# OP operand
AUX OV# DPO operand, which is the
inverse of AUX OV PKP
AUX OV# BLK setting for setting group γ. R
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
AUX UV# PKP operands
0, the code for unknown. It is unknown as
the element is non-directional
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R/C
R/W/C
R
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R