GE B30 Communications Manual page 364

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-150: Fault report settings data objects
LNName: FltRptRFLO#LDevice inst: CtrlUR element: FAULT REPORT # settings
data obj. data attribute
TapLocFlt
stVal
NumRcd
stVal
FltZ
cVal
cVal.mag.f
cVal.ang.f
3
RsStat
pulseConf ig
pulseConf ig
.cmdQual
pulseConf ig.onDurINT32U
pulseConf ig
.offDur
pulseConf ig
.numPls
ctlModel
sboT imeout
sboClass
operT imeout
InRef1
setSrcRef
setSrcCB
InRef2
setSrcRef
setSrcCB
Table 3-151: Fault report data file data objects
LNName: FltRFLOψψLDevice inst: CtrlUR element: Selected values from Fault Report Data f ile ψψ
data obj. data attribute
FltZ
cVal
cVal.mag.f
cVal.ang.f
FltRis
mag
mag.f
units
units.SIUnit
units.multiplier
FltLoopRis
mag
3-126
Type
FC UR Name
SPS
BOOLEAN
ST
TAP-LOCAL FAUL T
INS
INT32
ST
Modbus register 3020h, I.e.,
"Number of Fault Reports"
CMV
Vector
MX
FLOAT32
FLOAT32
SPC
PulseConf ig
CF
ENUMERATED
INT32U
INT32U
CtlModels
CF FltRptRFLO1.RsStat .ctlModel
INT32U
CF
SboClasses
CF
INT32U
CF
ORG
ObjectReference SP
FAUL T REPORT# TRIG.
ObjectReference SP
ORG
ObjectReference SP
CLEAR FAUL T REPORTS.
ObjectReference SP
Type
FC UR Name
CMV
Vector
MX
FLOAT32
Fault impedance magnitude in
primary ohms calculated as
shown below
FLOAT32
Fault impedance angle in
degrees calculated as shown
below
MV
AnalogueValue
MX
FLOAT32
Actual Value FAUL Tψψ FAUL T
RESIST converted to primary
ohms
Unit
CF
ENUMERATED
ENUMERATED
MV
AnalogueValue
MX
CHAPTER 3: IEC 61850 COMMUNICATION
Description
TAP-LOCAL FAUL T operand
Actual number of records
Mandatory data attribute which in this
case is f ixed at zero
0
0
instantiated only in FltRptRFLO1
0 (pulse)
2 ms (actually one pass)
0
1
30000
0 (operate-once)
0
FAUL T REPORT# TRIG.
reference to the data attribute to input
source GoCB of input if via GOOSE
Only instantiated in FltRptRFLO1
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
Mandatory data attribute which in this
case is f ixed at zero
FAUL Tψψ FAUL T RESIST converted to
primary ohms
30, the code for primary electric
resistance in ohm (V/A)
0, the code for a multiplier of 1
FAUL Tψψ LOOP RESIST converted to
primary ohms
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R/Ctrl
R
R
R
R
R
R/W/C
R
R
R
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R