MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: GndDisPDIS#
data obj. data attribute
phsC
NeutSupn
stVal
DpoPhsφ
stVal
BlkRefγ
setSrcRef
setSrcCB
3.5.2.28 Ground instantaneous overcurrent (GndIoc)
3
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60.
Table 3-53: Ground instantaneous overcurrent data objects
LNName: GndIocPIOC#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
BlkRefγ1
setSrcRef
setSrcCB
3.5.2.29 Ground time overcurrent (GndToc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60.
Table 3-54: Ground time overcurrent data objects
LNName: GndTocPTOC#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
BlkRefγ1
setSrcRef
setSrcCB
3.5.2.30 Hybrid permissive over-reaching transfer trip (HPOTT_)
This element is instantiated in the following products: D60, L90.
3-60
LDevice inst: Prot
UR element: Ground Distance Z# Settings
Type
FC UR Name
BOOLEAN
ST
GND DIST Z# OP C
SPS
BOOLEAN
ST
GND DIST Z# SUPN IN
SPS
BOOLEAN
ST
GND DIST Z#DPO θ
ORG
ObjectReference SP
GND DIST Z# BLK.
ObjectReference SP
LDevice inst: Prot
UR element: Ground Instantaneous Overcurrent element#
Type
FC UR Name
ACD
BOOLEAN
ST
GROUND IOC# PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
GROUND IOC# OP
SPS
BOOLEAN
ST
GROUND IOC# DPO
ORG
ObjectReference SP
GROUND IOC# BLOCK.
ObjectReference SP
LDevice inst: Prot
UR element: Ground Time Overcurrent element#
Type
FC UR Name
ACD
BOOLEAN
ST
GROUND TOC# PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
GROUND TOC# OP
SPS
BOOLEAN
ST
GROUND TOC# DPO
ORG
ObjectReference SP
GROUND TOC# BLOCK.
ObjectReference SP
CHAPTER 3: IEC 61850 COMMUNICATION
Description
GND DIST Z# SUPN IN operand
GND DIST Z# DPO θ operand
GND DIST Z# BLK setting for setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
GROUND IOC# PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
GROUND IOC# OP operand
GROUND IOC# DPO operand
GROUND IOC# BLOCK setting in setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
GROUND TOC# PKP operand, which
indicates Op will operate when delay
expires.
0, the code for unknown.
GROUND TOC# OP operand
GROUND TOC# DPO operand
GROUND TOC# BLOCK setting in setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C

Advertisement