GE B30 Communications Manual page 296

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: FldGnd1PHIZ1
data obj. data attribute
dirGeneral
Op
general
Dpo
stVal
Table 3-48: Field ground protection stage 2 objects
LNName: FldGnd2PHIZ1
data obj. data attribute
Str
3
general
dirGeneral
Op
general
Dpo
stVal
3.5.2.25 Frequency rate of change (RteHz)
This element is instantiated in the following products: D30, D60, F60, G30, G60, L30, L90, N60, T60.
Table 3-49: Frequency rate of change data objects
LNName: RteHzPFRC#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
HzChgRte
instMag
instMag.f
Mag
mag.f
units
units.SIUint
units.multiplier
db
zeroDb
BlkRef1
setSrcRef
setSrcCB
3-58
LDevice inst: Prot
UR element: FIELD GROUND element stage 1 functions
Type
FC UR Name
ENUMERATED
ST
ACT
BOOLEAN
ST
FIELD GND STG1 OP
SPS
BOOLEAN
ST
FIELD GND STG1 DPO
LDevice inst: Prot
UR element: FIELD GROUND element stage 2 functions
Type
FC UR Name
ACD
BOOLEAN
ST
FIELD GND STG2 PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
FIELD GND STG2 OP
SPS
BOOLEAN
ST
FIELD GND STG2 DPO
LDevice inst: Prot
UR element: Frequency Rate of Change element #
Type
FC UR Name
ACD
BOOLEAN
ST
FREQ RATE # PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
FREQ RATE # OP
SPS
BOOLEAN
ST
FREQ RATE # DPO
MV
AnalogueValue
MX
FLOAT32
FREQUENCY RATE OF CHANGE #
AnalogueValue
MX
FLOAT32
FREQUENCY RATE OF CHANGE #
on deadband exception
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
RteHzPFRC#.HzChgRte.db
INT32U
CF
ORG
ObjectReference SP
FREQ RATE # BLOCK.
ObjectReference SP
CHAPTER 3: IEC 61850 COMMUNICATION
Description
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
FIELD GND STG1 OP operand
FIELD GND STG1 DPO operand
Description
FIELD GND STG2 PKP operand
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
FIELD GND STG2 OP operand
FIELD GND STG2 DPO operand
Description
FREQ RATE # PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
FREQ RATE # OP operand
FREQ RATE # DPO operand
FREQUENCY RATE OF CHANGE # in Hz/s R
75, the code for Rate of change of
frequency (Hz/s)
0, the code for a multiplier of 1
0
FREQ RATE # BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R/C
R/C

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents