GE B30 Communications Manual page 346

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: PctDifPDIF1
data obj. data attribute
phsθ.dbAng
phsθ.zeroDb
angRef
BlkRefγ
setSrcRef
setSrcCB
3.5.2.76 Trip bus (TrBus)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
3
Table 3-126: Trip bus data objects
LNName: TrBusPTRC#
data obj. data attribute
Op
general
Str
general
dirGeneral
InRefαα
setSrcRef
setSrcCB
InRef99
setSrcRef
setSrcCB
BlkRef1
setSrcRef
setSrcCB
3.5.2.77 Trip output (TrOut)
This element is instantiated in the following products: C60, D60, L60, L90.
Table 3-127: Trip output data objects
LNName: TrOutPTRC1
data obj. data attribute
Tr
general
Tr3p
general
Tr1p
general
phsA
phsB
phsC
StrRec3p
3-108
LDevice inst: Prot
UR element: Transformer Percent Differential function
Type
FC UR Name
INT32U
CF
PctDifPDIF#.RstA.phsθ.dbAng
INT32U
CF
ENUMERATED
CF
ORG
ObjectReference SP
PERCENT DIFF BLOCK for group
γ.
ObjectReference SP
LDevice inst: Prot
UR element: Trip Bus element #
Type
FC UR Name
ACT
BOOLEAN
ST
TRIP BUS # OP
ACD
BOOLEAN
ST
TRIP BUS # PKP
ENUMERATED
ST
ORG
ObjectReference SP
TRIP BUS # INPUT α setting
ObjectReference SP
ORG
ObjectReference SP
TRIP BUS # RESET setting
ObjectReference SP
ORG
ObjectReference SP
TRIP BUS # BLOCK.
ObjectReference SP
LDevice inst: Prot
UR element: Trip Output element
Type
FC UR Name
ACT
BOOLEAN
ST
TRIP OUTPUT OP
ACT
BOOLEAN
ST
TRIP 3-POLE
ACT
BOOLEAN
ST
TRIP 1-POLE
BOOLEAN
ST
TRIP PHASE A
BOOLEAN
ST
TRIP PHASE B
BOOLEAN
ST
TRIP PHASE C
SPS
CHAPTER 3: IEC 61850 COMMUNICATION
Description
0
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
PERCENT DIFF BLOCK for setting group γ. R
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
TRIP BUS # OP operand, which becomes
On when any input is On, and the element
is not blocked
TRIP BUS # PKP operand, which indicates
Op will operate when delay expires.
0, the code for unknown
TRIP BUS # INPUT α setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
TRIP BUS # RESET setting, which when On
resets the non-volatile set-dominant
input conditions latch.
reference to the data attribute to input
source GoCB of input if via GOOSE
TRIP BUS # BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
TRIP OUTPUT OP (any trip) operand
TRIP 3-POLE operand
general is TRIP 1-POLE operand, phsA is
TRIP PHASE A operand, phsB is TRIP
PHASE B operand and phsC is TRIP PHASE
C operand
TRIP AR INIT 3-POLE operand
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R/W/C
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R