GE B30 Communications Manual page 317

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: NuVUn$PTOV#
data obj. data attribute
Type
ctlModel
CtlModels
Health
INS
stVal
ENUMERATED
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
BlkRefγ
ORG
GEORG
setSrcRef
ObjectReference SP
VISIBLE
STRING255
setSrcCB
ObjectReference SP
VISIBLE
STRING255
cdcNs
VISIBLE
STRING255
cdcName
VISIBLE
STRING255
3.5.2.48 Open pole detector (OpnPl)
This element is instantiated in the following products: C60, D60, L60, L90. It does not apply to open pole detector supervisor
N60.
Table 3-80: Open pole detector data objects
LNName: OpnPl0SCBR1
data obj. data attribute
Type
BlkRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
ColOpn
SPS
stVal
BOOLEAN
PlOpn
ACT
general
BOOLEAN
BlkPhDis
SPS
stVal
BOOLEAN
Table 3-81: Open pole detector data objects
LNName: OpnPlΘSCBR1
data obj. data attribute
Type
ColOpn
SPS
stVal
BOOLEAN
PlOpn
ACT
general
BOOLEAN
BkrOpnPl
ACT
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Neutral Voltage Unbalance element # stage $
FC UR Name
CF
ST
LPHD1.PhyHealth.stVal
ST
NTRL VOLT # STG$ PKP
ST
ST
NTRL VOLT # STG$ OP
NTRL VOL # BLK STG$ for group
γ
SP
SP
If reference is external to this
IED, mapped to the source's
GOOSE control block, else empty
string
EX
Name of the GE Multilin
namespace at the time of this
firmware release
EX
GEORG
LDevice inst: Prot
UR element: Open Pole Detector element
FC UR Name
OPEN POLE BLOCK
ST
Status of Logical OR condition to
OpnPl1SCBR1.ColOpn,
OpnPl2SCBR1.ColOpn,
OpnPl3SCBR1.ColOpn
ST
OPEN POLE OP
ST
OPEN POLE BLK N
LDevice inst: Prot
UR element: Open Pole Detector element for ψ and ψτ
FC UR Name
ST
Status value TRIP ψ setting
ST
OPEN POLE OP ψ
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
0 (status only)
This logical node's health
NTRL VOLT # STG$ PKP operand ".
0
NTRL VOLT # STG$ OP operand
NTRL VOL # BLK STG$ setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
OPEN POLE BLOCK setting
reference to the data attribute to input
source GoCB of input if via GOOSE
Logical OR of status value of mapped
FlexLogic operands in TRIP PHASE A, TRIP
PHASE B, TRIP PHASE C".
OPEN POLE OP operand
OPEN POLE BLK N operand
Description
Status value of mapped settings TRIP ψ R
OPEN POLE OP ψ operand
OPEN POLE BKR ψ OP operand
R/W/C
R
R
R
R
R
R
R
R
R
R
R/C
3
R/C
R/C
R/C
R
R
R/W/C
R
R/C
R/C
R
R
R
R
R
R
R/W/C
R
R
R
R
3-79