CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
46E2
...Repeated for Incipient Cable Fault
Detector 5
"
46EE
...Repeated for Incipient Cable Fault
Detector 6
Breaker Control (Read/Write Settings) (2, 3, 4, or 6 Modules)
All except B90
4740
Breaker 1 Function
"
4741
Breaker 1 Name
"
4744
Breaker 1 Mode
"
4745
Breaker 1 Open
"
4747
Breaker 1 Close
"
4749
Breaker 1 Phase A / Three-pole Closed
"
474B
Breaker 1 Phase B Closed
"
474D
Breaker 1 Phase C Closed
"
474F
Breaker 1 External Alarm
"
4751
Breaker 1 Alarm Delay
"
4753
Breaker 1 Pushbutton Control
"
4754
Breaker 1 Manual Close Recall Time
"
4756
Breaker 1 Out of Service
"
4758
Breaker 1 Block Open
"
475A
Breaker 1 Block Close
"
475C
Breaker 1 Phase A / Three-pole Opened
"
475E
Breaker 1 Phase B Opened
"
4760
Breaker 1 Phase C Opened
"
4762
Breaker 1 Operate Time
"
4764
Breaker 1 Open Seal In
"
4766
Breaker 1 Tagging
"
4767
Breaker 1 Substitution
"
4768
Breaker 1 Bypass
"
4769
Breaker 1 AR Block
"
476A
Breaker 1 Racked In
"
476C
Breaker 1 Events
"
476D
Reserved
"
477E
...Repeated for Breaker 2
B30, C60, C70,
479C
...Repeated for Breaker 3
D60, F60, F35,
L90, N60, T35,
T60
B30, C60, D60,
47CA
...Repeated for Breaker 4
F60, F35, L90,
N60, T35, T60
B30, F35, N60,
47F8
...Repeated for Breaker 5
T35, T60
"
4826
...Repeated for Breaker 6
Breaker Control Actual Values (Read Only) (2, 3, 4, or 6 Modules)
All except B90
4870
Breaker 1 States
"
4871
...Repeated for Breaker 2
B30, C60, C70,
4872
...Repeated for Breaker 3
D60, F60, F35,
L90, N60, T35,
T60
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
---
---
---
0 to 1
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 65.535
s
0.001 F003
0 to 1
---
1
0 to 65.535
s
0.001 F003
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 65535
ms
1
0 to 65.535
s
0.001 F003
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 4294967295
---
1
0 to 1
---
1
0 to 65535
s
1
0 to 14
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F206
"Bkr 1"
F157
0 (3-Pole)
F300
0
F300
0
F300
0
F300
0
F300
0
F300
0
0
F102
0 (Disabled)
0
F300
0
F300
0
F300
0
F300
0
F300
0
F300
0
F003
70
0
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F300
0
F102
0 (Disabled)
F001
0
F281
0 (CLOSED
BIT)