CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
TagOn
SPS
Breaker tagged.
The BREAKER 1 TAG ON operand.
TagOff
SPS
Breaker not tagged.
The BREAKER 1 TAG OFF operand.
TapLocFlt
SPS
L90 - The fault is identified between the local terminal and the tap point.
The TAP-LOCAL FAULT operand.
TdrTrbl
SPS
TDR trouble.
The TDR TROUBLE operand.
TempMnt
SPS
The ambient temperature is greater than the maximum operating temperature.
The TEMP MONITOR operand.
TestMod
SPS
LED indication - Relay in Test Mode.
The LED TEST MODE operand.
TestPrgInd
SPS
LED indication - Test In-Progress.
The LED TEST IN PROGRESS operand.
ThmCap
MV
% thermal model motor unbalance.
MOTOR THERMAL CAPACITY USED in percentage (%).
ThmLOTm
MV
Indicates Thermal Lockout for the motor.
THERMAL LOCKOUT TIME in seconds.
ThrdEthFail
SPS
Third Ethernet failure.
The THIRD ETHERNET FAIL operand.
TmChgOp1
SPS
Change in round trip delay on the channel exceeded pre-set value.
87L DIFF CH 1 TIME CHNG operand, which becomes On when the Change in round
trip delay on channel 1 exceeded preset value.
TmnsDelta
MV
PTP-IRIG-B Delta in ns
TmOfClc
INS
Represents the UTC time of the broken rotor bar calculation in seconds elapsed
since 1970/01/01, 00.00.00.
The TIME OF BRB CALC. actual value.
TmOfMax
INS
The TIME OF MAXIMUM BRB actual value
TmStr1
SPS
Power swing timer picked up.
The POWER SWING TMR2 PKP operand.
ToOilTmp
MV
Indicates top oil temperature.
The TOP OIL degrees C actual value.
TotLOTm
MV
Indicates total lockout time for the motor. TOTAL MOTOR LOCKOUT TIME in
seconds.
Tr1p
ACT
Single pole trip operation initiated.
The 87L TRIP 1P OP operand.
General is TRIP 1-POLE operand, phsA is TRIP PHASE A operand, phsB is TRIP
PHASE B operand, and phsC is TRIP PHASE C operand.
Tr3p
ACT
Three pole trip operation initiated.
The DCUB TRIP 3P operand.
The DIR BLOCK1 TRIP 3P operand.
The DUTT TRIP 3P operand.
The HYBRID POTT TRIP 3P operand.
The 87L TRIP 3P OP operand.
The POTT1 TRIP 3P operand.
The PUTT TRIP 3P operand.
The TRIP 3-POLE operand.
Tr3pFrcd
SPS
Three pole trip mode is being forced.
The TRIP FORCE 3-POLE operand (3-pole trip mode is being forced).
TransBlk
SPS
Phase comparison transient blocking has operated.
The 87PC TRANS BLOCK OP operand.
TrcHz
MV
B90 frequency
Trigger11
ENS
Represents the Hi-Z Data Capture 1 trigger type
Trigger21
ENS
Represents the Hi-Z Data Capture 1 RMS type
TripInd
SPS
LED indication - Element Trip Indication.
The LED TRIP operand.
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
Bkr0XCBR
Bkr0XCBR
FltRptRFLO
LPHD
LPHD
LEDsIHMI
LEDsIHMI
MotThmPTTR
MotThmPTTR
LPHD
LinDfPDIF
TmClkLTMS
BknRotSVBR
BknRotSVBR
PwrSwgRPSB
HPTmpSPTR
MotThmPTTR
LinDfPDIF, TrOutPTRC
DCB_PSCH, DCB1_PSCH,
DCUB_PSCH, DUTT_PSCH,
HPOTT_PSCH, LinDfPDIF,
POTT_PSCH, POTT1_PSCH,
PUTT_PSCH, TrOutPTRC
TrOutPTRC
PhCmp1PDIF
B_FrqMMXN
HiZPHIZ
HiZPHIZ
LEDsIHMI