GE B30 Communications Manual page 353

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: Sw8BitGAPC#
data obj. data attribute
Type
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef01
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.3.3 Automatic voltage regulator (Avr)
This element is instantiated in the following products: C70.
Table 3-138: Automatic voltage regulator data objects
LNName: AvrGAPC#
data obj. data attribute
Type
StrCls
SPS
stVal
BOOLEAN
OpCls
ACT
general
BOOLEAN
DpoCls
SPS
stVal
BOOLEAN
StrOpn
SPS
stVal
BOOLEAN
OpOpn
ACT
general
BOOLEAN
DpoOpn
SPS
stVal
BOOLEAN
BlkRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.3.4 B90 CT trouble (B_CtTb)
This element is instantiated in the following products: B90.
Table 3-139: B90 CT trouble data objects
LNName: B_CtTbPIOC#
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
3.5.3.5 Breaker arcing current (CBArc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T35,
T60.
Table 3-140: Breaker arcing current data objects
LNName: CBArc0SCBR#
data obj. data attribute
Type
AbrAlm
SPS
stVal
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
IntrAlm
SPS
stVal
BOOLEAN
IntrAlmDpo
SPS
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Ctrl
UR element: 8-Bit Switch #
FC UR Name
8BIT SW # ARG BΘ setting
8BIT SW # CONTROL setting
LDevice inst: Ctrl
UR element: Automatic Voltage Regulator # element
FC UR Name
ST
AVR # CLOSE PKP
ST
AVR # CLOSE OP
ST
AVR # CLOSE DPO
ST
AVR # OPEN PKP
ST
AVR # OPEN OP
ST
AVR OPEN # DPO
AVR # BLOCK
LDevice inst: Ctrl
UR element: B90 CT Trouble Zone element # function
FC UR Name
ST
CT TROUBLE ZONE# OP
LDevice inst: Ctrl
UR element: BREAKER # ARCING CURRENT element
FC UR Name
ST
BKR ARC # OP
ST
BKR ARC # DPO
ST
BKR ARC # MAX OP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
reference to the data attribute to input
source GoCB of input if via GOOSE
8BIT SW # CONTROL setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
AVR # CLOSE PKP operands.
AVR # CLOSE OP operand
AVR CLOSE # DPO operand
AVR # OPEN PKP operands.
AVR # OPEN OP operand
AVR OPEN # DPO operand
AVR # BLOCK setting
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
CT TROUBLE ZONE# OP operand
Description
BKR ARC # OP operand
BKR ARC # DPO operand
BKR ARC # MAX OP operand
BKR ARC # MAX DPO operand
R/W/C
R/C
R/C
R
R/C
R/C
R/W/C
3
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R/W/C
R
R
R
R
R
R
R
3-115

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents