GE B30 Communications Manual page 497

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 4: DNP COMMUNICATION
Object
Object
Variation
Description
no.
no.
23
5
32-Bit Frozen Counter Event with
cont'd
Time
6
16-Bit Frozen Counter Event with
Time
30
0
Analog Input (Variation 0 is used to
request default variation)
1
32-Bit Analog Input
2
16-Bit Analog Input
3
32-Bit Analog Input without Flag
4
16-Bit Analog Input without Flag
5
short floating point
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default
variations for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. See the Communications section in Chapter 5
of the Instruction Manual for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28,
respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for
change-event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts, meaning that the UR is not restarted, but the DNP process is restarted.
UR FAMILY – COMMUNICATIONS GUIDE
Request
Function codes
Qualifier codes
(dec)
(hex)
1 (read)
06 (no range, or all)
07, 08 (limited
quantity)
1 (read)
06 (no range, or all)
07, 08 (limited
quantity)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited
quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited
quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited
quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited
quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited
quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06(no range, or all)
07, 08(limited
quantity)
17, 28(index)
DEVICE PROFILE DOCUMENT
Response
Function codes
Qualifier codes
(dec)
(hex)
129 (response)
17, 28 (index)
130 (unsol. resp.)
129 (response)
17, 28 (index)
130 (unsol. resp.)
129 (response)
00, 01 (start-stop)
17, 28 (index)
(see Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index)
(see Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index)
(see Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index)
(see Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index)
(see Note 2)
4
4-7

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all