MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: PwrSwgRPSB1
data obj. data attribute
stVal
TmStr3
stVal
TmStr4
stVal
Blk
stVal
DistDet
stVal
InRefγ2
setSrcRef
3
setSrcCB
BlkRefγ
setSrcRef
setSrcCB
3.5.2.64 Restricted ground fault (RgDif)
This element is instantiated in the following products: F60, G30, G60, L90, T35, T60.
Table 3-110: Restricted ground fault data objects
LNName: RgDifPDIF#
data obj. data attribute
Op
general
Dpo
stVal
Str
general
dirGeneral
DifAClc
net
net.instCVal
net.instCVal.mag
.f
net.cVal
net.cVal.mag.f
net.units
net.units.SIUnit
net.units
.multiplier
net.db
net.zeroDb
RstA
net
net.instCVal
net.instCVal.mag
.f
net.cVal
net.cVal.mag.f
net.units
3-96
LDevice inst: Prot
UR element: Power Swing Detect element
Type
FC UR Name
BOOLEAN
ST
POWER SWING TMR2 PKP
SPS
BOOLEAN
ST
POWER SWING TMR3 PKP
SPS
BOOLEAN
ST
POWER SWING TMR4 PKP
SPS
BOOLEAN
ST
POWER SWING UN/BLOCK
SPS
BOOLEAN
ST
POWER SWING 50DD
ORG
ObjectReference SP
POWER SW I2 SUPV ENAB
setting
ObjectReference SP
ORG
ObjectReference SP
POWER SWING BLK.
ObjectReference SP
LDevice inst: Prot
UR element: Restricted Ground Fault # function
Type
FC UR Name
ACT
BOOLEAN
ST
RESTD GND FT# OP
SPS
BOOLEAN
ST
RESTD GND FT# DPO
ACD
BOOLEAN
ST
RESTD GND FT# PKP
ENUMERATED
ST
WYE
CMV
Vector
MX
FLOAT32
RGF# DIFF Igd magnitude, in
primary amps
Vector
MX
FLOAT32
RGF# DIFF Igd magnitude, in
primary amps, with deadband
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
RgDifPDIF#.DifAClc.net.db
INT32U
CF
WYE
CMV
Vector
MX
FLOAT32
RGF# RESTR Igr magnitude, in
primary amps
Vector
MX
FLOAT32
RGF# RESTR Igr magnitude, in
primary amps, with deadband
Unit
CF
CHAPTER 3: IEC 61850 COMMUNICATION
Description
POWER SWING TMR3 PKP operand
POWER SWING TMR4 PKP operand
POWER SWING UN/BLOCK operand
POWER SWING 50DD operand
POWER SW I2 SUPV ENAB setting for
setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
POWER SWING BLK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
RESTD GND FT# OP operands
RESTD GND FT# DPO operand
RESTD GND FT# PKP operand
1 is code for Forward
Differential currents
5, the code for amps
0, the code for a multiplier of 1
Restraint currents
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R