GE B30 Communications Manual page 287

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-35: Compensated overvoltage function data objects
LNName: CmpOv0PTOV1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
Table 3-36: Compensated overvoltage stage data objects
LNName: CmpOvPTOV$
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
3.5.2.16 Continuous monitor (CnMntr)
This element is instantiated in the following products: L90.
Table 3-37: Continuous monitor data objects
LNName: CnMntrGAPC1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
InRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef2
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef3
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef4
ORG
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Compensated Overvoltage functions
FC UR Name
ST
COMP OV PKP
ST
ST
COMP OV OP
ST
COMP OV DPO
COMPENSATED OV BLK for
group γ.
LDevice inst: Prot
UR element: Compensated Overvoltage stage $
FC UR Name
ST
COMP OV STG$ PKP
ST
ST
COMP OV STG$ OP
ST
COMP OV STG$ DPO
LDevice inst: Prot
UR element: Continuous Monitor element
FC UR Name
ST
CONT MONITOR PKP
ST
ST
CONT MONITOR OP
CONT MONITOR I-OP setting
Reference to the data object
selected by CONT MONITOR I-
SUPV
Reference to the data object
selected by CONT MONITOR V-
OP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
COMP OV PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
COMP OV OP operand
COMP OV DPO operand, which is the
inverse of COMP OV PKP
COMPENSATED OV BLK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
COMP OV STG$ PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
COMP OV STG$ OP operand
COMP OV STG$ DPO operand, which is
the inverse of COMP OV STG$ PKP
Description
CONT MONITOR PKP operand
0, the code for unknown
CONT MONITOR OP operand
CONT MONITOR I-OP setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
CONT MONITOR I-SUPV setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
CONT MONITOR V-OP setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
CONT MONITOR V-SUPV setting.
R/W/C
R
R
R
R
R
R
R
R
R/C
3
R/C
R/W/C
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R