GE B30 Communications Manual page 270

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: LLN0
data obj. data attribute
operTimeout
GrRef
setSrcRef
MltLev
setVal
<TTΣDataS
et##>
3
DSMemberRef[η] ObjectReference
3.5.1.3 Physical device information (LPHD1)
LPHD1 is instantiated in all UR family devices.
Table 3-12: Physical device data objects
LNName: LPHD1LDevice inst: MasterUR element:
data obj. data attribute
PhyNam
vendor
swRev
serNum
model
location
name
latitude
longitude
altitude
PhyHealt
h
stVal
Proxy
stVal
RsStat
pulseConf ig
pulseConf ig
pulseConf ig.onD INT32
pulseConf ig
pulseConf ig
ctlModel
sboT imeout
sboClass
3-32
LDevice inst: Master
UR element: Nameplate information for the logical nodes
Type
FC UR Name
INT32U
CF
ORG
ObjectReference SP
For communications, mapped to
Master ldName if not empty,
otherwise to the concatenation
of the IED name and "Master".
For SCL, mapped to the
concatenation of the IED name
and "Master".
SPG
BOOLEAN
SP
DATA-SET
DataSet Member η
Type
FC UR Name
DPL
VISIBLE
DC "GE Multilin"
VISIBLE
DC Firmware revision, e.g. "7.30"
VISIBLE
DC The serial number of this unit .
VISIBLE
DC The order code of this unit .
VISIBLE
DC Location
VISIBLE
DC RELAY NAME
FLOAT32
DC Latitude
FLOAT32
DC Longitude
FLOAT32
DC Altitude
ENS
ENUMERATED
ST
SPS
BOOLEAN
ST
SPC
PulseConf ig
CF
ENUMERATED
INT32
INT32
CtlModels
CF
LPHD1.RsStat .ctlModel
INT32U
CF
SboClasses
CF
CHAPTER 3: IEC 61850 COMMUNICATION
Description
0
Reference to root logical device
reference to the data attribute to input
Instantiated only in the Master logical
device
Description
This physical device's name plate
This physical device's health
3 when ANY MAJOR ERROR==On; 2
Indicates if this LN is a proxy
Mapped to command CLEAR ALL RELAY R/Ctrl
0 (pulse)
0 indicates the duration is locally
0
1
1, the code for direct control with normal
security; 2 is code for SBO with normal
security; 0 is for status only according to
IEC 61850-7-2. Enhanced security is not
supported as there is no means of
conf irming successful execution of the
30000
0 (operate-once)
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R/C
R/W/C
R
R
R
R
R
R/C
R/C
R/C
R/C
R/C
R
R
R
R
R
R
R
R
R
R/C
R
R

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents