CHAPTER 3: IEC 61850 COMMUNICATION
LNName: LosExt1PDIS1
data obj. data attribute
Type
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
Table 3-64: Loss of excitation stage 2 objects
LNName: LosExt2PDIS1
data obj. data attribute
Type
Mod
INC
stVal
ENUMERATED
ctlModel
CtlModels
Health
INS
stVal
ENUMERATED
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
3.5.2.35 Mechanical jam (MecJam)
This element is instantiated in the following products: M60.
Table 3-65: Mechanical jam data objects
LNName: MecJamPMSS1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.36 Motor acceleration time (MAccTm)
This element is instantiated in the following products: M60.
Table 3-66: Motor acceleration time data objects
LNName: MAccTmPMSS1
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
Dpo
SPS
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Loss of Excitation element stage 1 functions
FC UR Name
ST
LOSS EXCIT STG1 PKP
ST
ST
LOSS EXCIT STG1 OP
ST
LOSS EXCIT STG1 DPO
LDevice inst: Prot
UR element: Loss of Excitation stage 2 functions
FC UR Name
ST
CF
ST
LPHD1.PhyHealth.stVal
ST
LOSS EXCIT STG2 PKP
ST
ST
LOSS EXCIT STG2 OP
ST
LOSS EXCIT STG2 DPO
LDevice inst: Prot
UR element: MECHANICAL JAM element
FC UR Name
ST
MECHANICAL JAM PKP
ST
ST
MECHANICAL JAM OP
ST
MECHANICAL JAM DPO
MECH JAM BLK for group γ
LDevice inst: Prot
UR element: Acceleration Time element
FC UR Name
ST
MOTOR ACCEL TIME OP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
0
LOSS EXCIT STG1 OP operand
LOSS EXCIT STG1 DPO operand
Description
This logical node's mode
1 (on)
0 (status only)
This logical node's health
LOSS EXCIT STG2 PKP operand
0
LOSS EXCIT STG2 OP operand
LOSS EXCIT STG2 DPO operand
Description
MECHANICAL JAM PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
MECHANICAL JAM OP operand
MECHANICAL JAM DPO operand, which is
the inverse of MECHANICAL JAM PKP
MECH JAM BLK setting for setting group γR
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
MOTOR ACCEL TIME OP operand
MOTOR ACCEL TIME DPO operand
R/W/C
R
R
R
R
R
R
R/W/C
R/Ctrl
3
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R