CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
RlyUTCTms
INS
Represents the relay UTC time in seconds elapsed since 00:00:00 January 1, 1970.
Mapped to Modbus register 41A0h value, that is, "Relay time clock set time"
register value after converting to UTC (if time zone and DST is used).
RrtdComFail
SPS
RRTD communication failure.
The RRTD COMM FAIL operand.
Rs
SPS
Autoreclose has been reset either manually or by the rest timer.
The AR RESET operand.
RsOp
SPS
Target resetting - General indication (binary input).
The RESET OP operand value.
RsOpLoc
SPS
Target resetting - General indication (binary input).
The RESET OP (OPERAND) operand value.
RsOpPB
SPS
Target resetting - General indication (binary input).
The RESET OP (PUSHBUTTON) operand value.
RsOpRem
SPS
Target resetting - General indication (binary input).
The RESET OP (COMMS) operand value.
RsTms
INS
The UTC time of the last clear in seconds elapsed since 00:00:00 January 1, 1970.
The LAST CLEARED DATE actual value.
RtdTrbl
SPS
RTD trouble.
The RTD TROUBLE operand.
Running
SPS
Indicate the motor is running.
The MOTOR RUNNING operand.
RvOp
SPS
Fault direction is reverse.
The NEG SEQ DIR OC1 REV operand.
The NTRL DIR OC1 REV operand.
RX1
SPS
Pulse received on channel 1 or 2.
The 87PC RX1 operand.
RxGooseOff
SPS
One or more RxGOOSE is not responding.
The RxGOOSE OFF operand.
Sat1
SPS
Indicates CT saturation is detected.
The BUS 1 SAT A/B/C operand.
Sat1
SPS
Indicates phase saturation of differential is detected per phase
The STATOR DIFF1 SAT A/B/C operand.
SbstCls
SPS
Manually substituted to close.
The BREAKER 1 SUBD CLSD operand.
SbstOpn
SPS
Manually substituted to open.
The BREAKER 1 SUBD OPEN operand.
SecDataClr
SPC
Command CLEAR SECURITY DATA, TRUE = CLEAR SECURITY DATA
SecEna
ENG
RxRGOOSE1 Security Ena setting: 0=None; 1=Signature; 2=Signature and
Encryption. Otherwise ignored.
SecEthFail
SPS
Second Ethernet failure.
The SECOND ETHERNET FAIL operand.
SecondOfDay
INS
Represents integer number of seconds past midnight (Range1-86400).
The SecondOfDay actual value in seconds.
SeqTO
SPS
The incomplete sequence timer timed out.
The AR INCOMPLETE SEQ operand.
SHAmpAng
MV
Sub harmonic current angle.
SH CURRENT ANGLE in degrees.
ShotCnt1
SPS
Autoreclosec shot count is equal to the number indicated by the data instance
number.
The AR SHOT CNT=1 operand.
ShrtCirc
SPS
Short circuit detected.
The RRTD RTD 1 SHORTED operand.
The RTD Ip 1 SHORTED operand.
Sim
SPC
Simulated GOOSE values or simulated sampled measurand values are used
instead of original values since they are first received
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
LPHD
LPHD
Rec13pRREC
TgtRsIHMI
TgtRsIHMI
TgtRsIHMI
TgtRsIHMI
OscRDRE
LPHD
MotThmPTTR
NegDocRDIR, NeuDocRDIR
PhCmp1PDIF
LPHD
B_DifPDIF, BusDifPDIF
SttDifPDIF
Bkr0XCBR
Bkr0XCBR
SecGSAL
LGOS
LPHD
TmDayGAPC
Rec13pRREC
SubHaPHIZ
Rec13pRREC, Rec3pRREC
PRTDsSTMP, RRTDsSTMP
LPHD
3-215