GE B30 Communications Manual page 356

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: BkrRtkPIOC#
data obj. data attribute
Op
general
phsA
phsB
phsC
BlkRef1
setSrcRef
setSrcCB
3
cdcNs
cdcName
InRef1
setSrcRef
setSrcCB
cdcNs
cdcName
InRef2
setSrcRef
setSrcCB
cdcNs
cdcName
InRef3
setSrcRef
setSrcCB
3-118
LDevice inst: Ctrl
UR element: Breaker Control element #
Type
FC UR Name
ACT
BOOLEAN
ST
BRK RESTIRKE # OP
BOOLEAN
ST
BRK RESTIRKE # OP A
BOOLEAN
ST
BRK RESTIRKE # OP B
BOOLEAN
ST
BRK RESTIRKE # OP C
ORG
GEORG
ObjectReference SP
BKR RSTR # BLOCK.
VISIBLE
SP
Reference to the ultimate source
STRING255
of value selected by setting BKR
RSTR # BLOCK.
ObjectReference SP
VISIBLE
SP
If reference is external to this
STRING255
IED, mapped to the source's
GOOSE control block, else empty
string
VISIBLE
EX
Name of the GE Multilin
STRING255
namespace at the time of this
firmware release
VISIBLE
EX
GEORG
STRING255
ORG
GEORG
ObjectReference SP
BKR RSTR # BKR OPEN.
VISIBLE
SP
Reference to the ultimate source
STRING255
of value selected by setting BKR
RSTR # BKR OPEN.
ObjectReference SP
VISIBLE
SP
If reference is external to this
STRING255
IED, mapped to the source's
GOOSE control block, else empty
string
VISIBLE
EX
Name of the GE Multilin
STRING255
namespace at the time of this
firmware release
VISIBLE
EX
GEORG
STRING255
ORG
GEORG
ObjectReference SP
BKR RSTR # OPEN CMD.
VISIBLE
SP
Reference to the ultimate source
STRING255
of value selected by setting BKR
RSTR # OPEN CMD.
ObjectReference SP
VISIBLE
SP
If reference is external to this
STRING255
IED, mapped to the source's
GOOSE control block, else empty
string
VISIBLE
EX
Name of the GE Multilin
STRING255
namespace at the time of this
firmware release
VISIBLE
EX
GEORG
STRING255
ORG
GEORG
ObjectReference SP
BKR RSTR # CLS CMD.
VISIBLE
SP
Reference to the ultimate source
STRING255
of value selected by setting BKR
RSTR # CLS CMD.
ObjectReference SP
CHAPTER 3: IEC 61850 COMMUNICATION
Description
BRK RESTIRKE # OP operand (including
individual three phases)
BKR RSTR # BLOCK setting
reference to the data attribute to input
source GoCB of input if via GOOSE
BKR RSTR # BKR OPEN setting
reference to the data attribute to input
source GoCB of input if via GOOSE
BKR RSTR # OPEN CMD setting
reference to the data attribute to input
source GoCB of input if via GOOSE
BKR RSTR # CLS CMD setting
reference to the data attribute to input
source GoCB of input if via GOOSE
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R/C
R/C
R/C
R/C
R
R
R
R
R/C
R/C
R/C
R/C
R
R
R
R
R/C
R/C
R/C
R/C
R
R
R
R
R/C
R/C
R/C