GE B30 Communications Manual page 444

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Data object
CDC
name
BkrOp1
SPS
BkrOpnPl
ACT
Blk2ndH1
SPS
Blk5thH1
SPS
BlkH1
SPS
3
BlkPhDis
SPS
BrckTrbl
SPS
BRstA
CMV
BusV0
CMV
BusVPh
WYE
BypsOff
SPS
BypsOn
SPS
ChA
CMV
ChFail1
SPS
ChV
CMV
ClkUnsynch
SPS
ClrMem
SPC
Cls2ndBkr
SPS
ClsSt1
SPS
CmpCt1I1
MV
CmpCt1I2
MV
CompAop
MV
CompAPh
WYE
CompHz
MV
CompLevel
MV
ConfRev
ING
CrcFail1
SPS
Ctrl
SPS
CurUnb
MV
Day1
SPS
3-206
Semantics
Breaker failure status information operands. The BKR FAIL 1 T1 OP operand.
Indicates open pole condition is detected in phase A, B, or C based on the breaker
auxiliary contacts. The OPEN POLE BKR phase A/B/C OP operand.
Indicates second harmonic blocking active (where the last digit of instance
number 1, 2, or 3 refers to phase A, B, and C respectively).
The XFMR PCNT DIFF 2ND A/B/C operand.
Indicates fifth harmonic blocking active (where the last digit of instance number
1, 2, or 3 refers to phase A, B, and C respectively).
The XFMR PCNT DIFF 5TH A/B/C operand.
The second harmonic of the transformer magnetizing inrush current has inhibited
the current differential element from operating.
The 87L HARM2 A/B/C OP operand, which becomes asserted when phase A/B/C
of second harmonic of the transformer magnetizing inrush current inhibits the
current differential element from operating.
Indicates blocking signal for neutral, ground, or negative sequence overcurrent
elements. The OPEN POLE BLK Phase AB/BC/CA/N operand.
Brick trouble. The BRICK TROUBLE operand.
B90 restraint current
Zero Sequence Bus voltage in pu
Bus voltage in per unit for phase A, B, and C
Control interlocking is not manually bypassed.
The BREAKER 1 BYPASS OFF operand.
Control interlocking is manually bypassed.
The BREAKER 1 BYPASS ON operand.
B90's AC channel current
Communications channel failed.
The 87L DIFF CH 1 FAIL operand, which becomes On when the differential element
has detected communications channel 1 failed.
B90's AC channel voltage
Relay is not synchronized to the international time standard.
The CLOCK UNSYNCHRONIZED operand.
Clear Hi-Z oscillography
Close second Breaker signal. The AR CLOSE BKR2 operand.
Close status detected.
The BREAKER/SWITCH CLOSED operand.
Compensated I1 current magnitude for CT bank 1.
CT1 COMP I1 Mag in amperes.
Compensated I2 current magnitude for CT bank 1.
CT2 COMP I1 Mag in amperes.
Compensated operating current. Comp Iop in per unit.
Cm Iop in per unit for Phase A, B, and C
Indicates the frequency of the broken rotor bar spectral component.
The COMPONENT FREQ. in Hz.
Indicates the level of the broken rotor bar spectral component relative to the
spectral component of the system frequency.
The COMPONENT LEVEL in dB.
Expected value of confRev field in messages subscribed to by RxGOOSE#
The CRC error threshold has been exceeded.
The 87L DIFF CH 1 CRCFAIL operand, which becomes On when the differential
element has detected the CRC error threshold has been exceeded on channel 1.
Asserted for one second upon any transition in any mode
% UNBALANCE CURRENT
Current day, where 1 = Sunday. The DAY operand.
CHAPTER 3: IEC 61850 COMMUNICATION
Used in logical nodes...
BkrFaRBRF, B_BFaiRBRF
OpnPlΘSCBR
PctDifPDIF
PctDifPDIF
LinDfPDIF (L90)
OpnPlΘSCBR
LPHD
B_DifPDIF
NuVUnPTOV
VDifPDIF
Bkr0XCBR
Bkr0XCBR
B_AmpMMXN
LinDfPDIF
B_VolMMXN
LPHD
HiZPHIZ
Rec13pRREC
BkrΘXCBR, Bkr0XCBR,
Disc0XSWI, DiscΘXSWI,
GGIO3
PhCmp1PDIF
PhCmp1PDIF
NeAUnPTOC
PhAUnPTOC
BknRotSVBR
BknRotSVBR
LGOS
LinDfPDIF
LoVStrGAPC
AmpUnbPTOC
TmDayGAPC