MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-114: Sensitive directional power stage 1 data objects
LNName: Sen1PDOP#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
3
Table 3-115: Sensitive directional power stage 2 data objects
LNName: Sen2PDOP#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
3.5.2.68 Speed 2 motor acceleration time (S2AcTm)
This element is instantiated in the following products: M60.
Table 3-116: Speed 2 acceleration time data objects
LNName: S2AcTmPMSS1
data obj. data attribute
Mod
stVal
ctlModel
Health
stVal
Op
general
Dpo
stVal
SPDTR
stVal
BlkRefγ
setSrcRef
setSrcCB
3-100
LDevice inst: Prot
UR element: Sensitive Directional Power element # stage 1 functions
Type
FC UR Name
ACD
BOOLEAN
ST
DIR POWER # STG1 PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
DIR POWER # STG1 OP
SPS
BOOLEAN
ST
DIR POWER # STG1 DPO
LDevice inst: Prot
UR element: Sensitive Directional Power element # stage 2 functions
Type
FC UR Name
ACD
BOOLEAN
ST
DIR POWER # STG2 PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
DIR POWER # STG2 OP
SPS
BOOLEAN
ST
DIR POWER # STG2 DPO
LDevice inst: Prot
UR element: SPEED2 Acceleration Time element
Type
FC UR Name
INC
ENUMERATED
ST
CtlModels
CF
INS
ENUMERATED
ST
LPHD1.PhyHealth.stVal
ACT
BOOLEAN
ST
MOTOR SPD2 ACL t OP
SPS
BOOLEAN
ST
MOTOR SPD2 ACL t DPO
SPS
BOOLEAN
ST
MOTOR SPD2 TR 2-1 OP
ORG
GEORG
ObjectReference SP
SPEED2 ACCEL BLOCK.
VISIBLE
SP
Reference to the ultimate source
STRING255
of value selected by setting
SPEED2 ACCEL BLOCK.
ObjectReference SP
CHAPTER 3: IEC 61850 COMMUNICATION
Description
DIR POWER # STG1 PKP operand, which
becomes On when the directional power
comparator has operated.
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
DIR POWER # STG1 OP operand
DIR POWER # STG1 DPO operand, which
is the inverse of DIR POWER STG1 OP
Description
DIR POWER # STG2 PKP operand, which
becomes On when the directional power
comparator has operated.
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
DIR POWER # STG2 OP operand
DIR POWER # STG2 DPO operand, which
is the inverse of DIR POWER STG2 OP
Description
This logical node's mode
1 (on)
0 (status only)
This logical node's health
MOTOR SPD2 ACL t OP operand
MOTOR SPD2 ACL t DPO operand
MOTOR SPD2 TR 2-1 OP operand
SPEED2 ACCEL BLOCK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R/W/C
R/Ctrl
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R/C

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents