MEMORY MAP
Products
Address Register name
"
60E7
"
60E8
"
60E9
"
60EB
2
"
60EC
"
60F0
"
60F2
"
60F8
"
60FD
"
6104
"
6106
"
6107
"
6108
"
6109
"
610A
"
610B
"
610C
"
610E
"
6110
"
6111
"
6112
"
6113
"
6114
"
6115
"
6117
"
6118
"
611A
Continuous Monitor (Read/Write Setting)
L90
6130
"
6131
"
6133
"
6135
"
6137
"
6139
"
613A
Transformer Hottest Spot (Read/Write Grouped Setting)
G30, T35, T60
6140
"
6141
"
6142
"
6143
"
6145
"
6146
Transformer Aging Factor (Read/Write Grouped Setting)
G30, T35, T60
6150
2-80
87PC Scheme Signal
87PC Signal Source
87PC FDL Pickup
87PC FDH Pickup
87PC Mixed Signal K
87PC Phase Delay Ch1
87PC Phase Delay Ch2
87PC Transient Pickup
87PC Asymmetry Channel 1
87PC Asymmetry Channel 2
87PC Stability Angle
87PC Transient Reset
87PC Received Volts Channel 1
87PC Received Volts Channel 2
87PC High-Speed Contact 1
87PC High-Speed Contact 2
87PC FDL AUX
87PC FDH AUX
87PC Reset Delay
87PC Mixed Signal Reference Angle
87PC Trip Security
87PC Second Coincidence Timer
87PC Enhanced Stability Angle
87PC FDH Supervision
87PC Pickup Delay
87PC Stop Tx
87PC Tx Reset Delay
Continuous Monitor Function
Continuous Monitor I (current) OP
Continuous Monitor I (current) Supervision
Continuous Monitor V (voltage) OP
Continuous Monitor V (voltage) Supervision 0 to 4294967295
Continuous Monitor Target
Continuous Monitor Events
Transformer Hottest Spot Function
Transformer Hottest Spot Pickup
Transformer Hottest Spot Delay
Transformer Hottest Spot Block
Transformer Hottest Spot Target
Transformer Hottest Spot Events
Transformer Aging Factor Function
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
0 to 2
---
1
0 to 1
---
1
0.02 to 15
pu
0.01
0.05 to 15
pu
0.01
0 to 0.25
---
0.01
0 to 30
ms
0.1
0 to 30
ms
0.1
0 to 65.535
s
0.001 F001
-5 to 5
ms
0.1
-5 to 5
ms
0.1
40 to 140
degrees 5
0 to 65.535
s
0.001 F001
0 to 125
V
0.1
0 to 125
V
0.1
0 to 64
---
1
0 to 64
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 200
ms
1
0 to 359
°
1
0 to 1
---
1
10 to 200
ms
1
40 to 180
°
5
0 to 4294967295
---
1
0 to 50
ms
1
0 to 4294967295
---
1
0 to 1000
ms
1
0 to 1
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
50 to 300
°C
1
0 to 30000
min
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
UR FAMILY – COMMUNICATIONS GUIDE
Format
Default
F150
0 (MIXED I_2
- K*I_1)
F089
0 (One
Source
Current)
F001
50
F001
75
F001
20
F001
0
F001
0
30
F002
0
F002
0
F001
75
30
F001
120
F001
120
F490
0
F490
0
F300
0
F300
0
F001
30
F001
0
F534
0 (First
Coincidence)
F001
40
F001
110
F300
0
F001
0
F300
0
F001
0
F102
0 (Disabled)
F300
0
F300
0
F300
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
140
F001
1
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents