CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
NeutSupn
SPS
Neutral overcurrent supervision status.
The GND DIST Z1 SUPN IN operand.
NeutVx
CMV
Neutral point voltage in pu
NumCycPer
INS
Number of cycles of the nominal frequency. The CYCLES PER RECORD actual
value.
Off
SPS
Logic 0 fixed operand
Offline
SPS
Indicate the motor is offline.
The MOTOR OFFLINE operand.
On
SPS
Logic 1 fixed operand
OnePoleOpn
SPS
One pole is open, others closed.
The BREAKER 1 ONE P OPEN operand.
OnePU
ASG
The per-unit base factor applied to the corresponding RxGOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity.
OpAlm
ACT
Operate indicates the alarm decision of a protection function.
The U/CURR ALARM OP operand.
The UNDERPWR 1 ALARM OP operand.
OpBia
ACT
B90 Operate indicates the trip decision of a biased protection logic
OpHiSet
ACT
B90 Operate indicates the trip decision of the HISET element of breaker failure
current supervision function.
OpLoSet
ACT
B90 Operate indicates the trip decision of the LOSET element of breaker failure
current supervision function.
OpnCirc
SPS
Open circuit detected.
The RRTD RTD 1 OPEN operand.
The RTD Ip 1 OPEN operand.
OpnSt1
SPS
Open status detected.
The BREAKER/SWITCH OPEN operand.
The RxGOOSE DPS1 Off operand.
OpPhs1
SPS
Indicates a trip decision for a particular cause per phase.
The BUS 1 BIASED OP A/B/C operand.
The BUS 1 UNBIASED OP A/B/C operand.
The PHS DIST Z1 OP AB/BC/CA operand.
OpSig
MV
Operating signal, the analogue value used by the comparator.
FLEXELEMENT 1 OpSig, in per unit.
OpUnBia
ACT
B90 Operate indicates the trip decision of an unbiased protection logic
OpV
WYE
Phase Operating Voltages.
Bank Operating Voltage in per unit for Phase A, B, and C.
OscilGOOSE
SPS
One or more of GGIO1.Ind###.stVal has been frozen due to frequent status
changes (chatter) in the mapped operand.
The Oscillatory GOOSE operand.
OtherInd
SPS
An LED.
The LED OTHER operand.
OvlTripTm
MV
Indicates estimation of trip time on overload.
The ESTIMATED TRIP TIME ON OVERLOAD in seconds.
OutOfSrv
SPS
Out-of-service.
The BREAKER 1 OOS operand.
P1Rip
SPS
Autoreclose A single pole is in progress.
The AR 1-P RIP operand.
P3Rip1
SPS
Autoreclose 3-pole is in progress via dead time number indicated by the data
instance number.
The AR 3-P/1 RIP operand.
P3Tr
SPS
Force any trip to 3-phase trip.
The AR FORCE 3-P TRIP operand.
PFLLfail
SPS
Phase and/or frequency lock loop (PFLL) has failed.
The 87L DIFF PFLL FAIL operand, which becomes On when the differential
element's phase and frequency lock loop (PFLL) has failed.
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
GndDisPDIS
NuVUnPTOV
OscRDRE
Master/LLN0
MotThmPTTR
Master/LLN0
Bkr0XCBR
GGIO3
UnCurPTUC, UnPwrPDUP
B_DifPDIF
B_BFaiPIOC
B_BFaiPIOC
PRTDsSTMP, RRTDsSTMP
BkrΘXCBR, Bkr0XCBR,
Disc0XSWI, DiscΘXSWI,
GGIO3
BusDifPDIF, PhsDisPDIS
FlxElGAPC
B_DifPDIF
CPhOvPTOV
LPHD
LEDsIHMI
MotThmPTTR
Bkr0XCBR
Rec13pRREC
Rec13pRREC
Rec13pRREC
LinDfPDIF
3-213
3