GE B30 Communications Manual page 443

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
Agnd
CMV
Ground current (fourth input in a current AC bank).
SRC 1 Ground Current phasor, in primary amperes.
AgndRMS
MV
Ground current RMS (fourth input in a current AC bank).
SRC 1 Ground Current RMS, in primary amperes.
AlgCap
SPC
Command for the Hi-Z Oscillography Force Algorithm Capture
AlmInd
SPS
An LED.
The LED ALARM operand.
AmpInd
SPS
An LED.
The LED CURRENT operand.
AnFailBeh
ENG
Setting to select the behavior of the RxGOOSE Analog when the sending device is
offline: 0 = Default Value, 1 = Last Known
AnFailVal
ASG
The value of the RxGOOSE Analog when the sending device is offline and the
FailBeh is set to "Default Value"
AnOutput1
MV
Analog output
AnyPBOn
SPS
Indicates ANY PB ON operand state. When any of the user pushbuttons is
asserted, status is "true"; when none of the user pushbuttons are asserted, status
is "false."
AnyErr
SPS
Any of the self-test errors generated. The ANY SELF TESTS operand.
AnyGpsFail
SPS
The GPS signal failed or is not configured properly at any terminal.
The 87L DIFF GPS FAIL operand, which becomes On when the GPS signal failed or
is not configured properly at any terminal.
AnyPoleOpn
SPS
At least one pole is open. The BREAKER 1 ANY P OPEN operand.
AnyShotCnt
SPS
The first breaker close signal has been issued.
The AR SHOT CNT greater than zero operand.
APPID
ING
Expected value of APPID field in messages subscribed to by RxGOOSE#
The RxGOOSE1 ETYPE APPID setting.
ArBlk1
SPS
Autoreclose Breaker number indicated by the data instance number is
temporarily disabled.
The AR BKR1 BLK operand and the AR1 BLK FROM MAN CLS operand.
ArcConfid1
INS
Represents the Arc Confidence in percentage for Phase A, B, C, or N
ArcSuspect
ACT
Indicates suspected element has operated
AresRMS
MV
Residual Current RMS.
SRC 1 Neutral Current RMS, in primary amperes.
ArLO
SPS
Autoreclose is locked out. The AR LO operand.
Armed
SPS
Accidental energization. Occurs when the generator is offline with no fault
involved. The ACCDNT ENRG ARMED operand.
ArMod1
SPS
Autoreclosec mode equals to the number indicated by the data instance number,
in this case 1 and 3 pole mode. The AR MODE = 1 operand.
ArRip
SPS
Autoreclose is in progress. The AR RIP operand.
ASupn1
SPS
Indicates the state of current supervision.
The PHS DIST Z1 SUPN AB/BC/CA operand in Phase-To-Phase.
Asymmetry
SPS
Communications channel asymmetry detected.
The 87L DIFF CH ASYM DET operand, which becomes On when the differential
element's has detected substantial communications channel asymmetry.
AutoMod
SPS
Capacitor control in auto mode. The CAP 1 IN AUTO operand.
BadSt1
SPS
Bad-status detected. The BREAKER/SWITCH BAD STATUS operand.
BatFail
SPS
The battery is not functioning. The BATTERY FAIL operand.
BDifAClc
CMV
B90 differential current
BiasMotLod
MV
Indicates thermal model biased motor load.
THERMAL MODEL BIASED MOTOR LOAD in x FLA.
BknRotClr
SPC
Command to Clear BROKEN ROTOR BAR DATA. TRUE= CLEAR BROKEN ROTOR BAR
DATA
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
ACsrcMMXN
ACsrcMMXN
HiZPHIZ
LEDsIHMI
LEDsIHMI
GGIO3
GGIO3
Cmp8BtGAPC
UsrPbIHMI
LPHD
LinDfPDIF
Bkr0XCBR
Rec13pRREC
LGOS
Rec13pRREC, Rec3pRREC
HiZPHIZ
HiZPHIZ
ACsrcMMXU
Rec13pRREC, Rec3pRREC
AcdEnrPIOC
Rec13pRREC
Rec13pRREC, Rec3pRREC
PhsDisPDIS
LinDfPDIF
CapCtlGAPC
BkrΘXCBR, Bkr0XCBR,
Disc0XSWI, DiscΘXSWI,
GGIO3
LPHD
B_DifPDIF
MotThmPTTR
BknRotSVBR
3-205
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all