CHAPTER 3: IEC 61850 COMMUNICATION
LNName: ACsrcMMXU#
data obj. data attribute
Type
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
AcRMS
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
AresRMS
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
Adif
CMV
instCVal
Vector
instCVal.mag.f
FLOAT32
instCVal.ang.f
FLOAT32
cVal
Vector
cVal.mag.f
FLOAT32
cVal.ang.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
dbAng
INT32U
zeroDb
INT32U
angRef
ENUMERATED
W
WYE
phsA
CMV
phsA.instCVal
Vector
phsA.instCVal.mag
FLOAT32
.f
phsA.cVal
Vector
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Meter
UR element: AC Source #
FC UR Name
MX
CF
CF
MMXU# RMS A.phsB DEADBAND
CF
MX
SRC # Phase C Current RMS
MX
CF
CF
MMXU# RMS A.phsC DEADBAND
CF
MX
SRC # Neutral Current RMS
MX
CF
CF
MMXU# RMS A.neut DEADBAND
CF
MX
SRC # Differential Ground
Current Magnitude
SRC # Differential Ground
Current Angle
MX
CF
CF
MMXU# Dif Gnd Cur.db
CF
MMXU# Dif Gnd Cur.dbAng
CF
CF
MX
SRC # Phase A Real Power
MX
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
instMag.f deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
current cut-off level.
SRC # Phase C Current RMS, in primary
amperes
instMag.f deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
current cut-off level.
SRC # Neutral Current RMS, in primary
amperes
instMag.f deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
current cut-off level.
SRC # Differential Ground Current phasor,
in primary amperes
UR range -180...+180 converted to 0...360 R
instCVal.mag.f deadbanded
instCVal.ang.f deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
current cut-off level.
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
SRC # Phase Real Power, in primary wattsR
R/W/C
R
R
R
R
R
R/W/C
R
R
R
R
R
3
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R
R
R
3-175