MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-121: Subharmonic stator ground data objects
LNName: SubHaPHIZ1
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
Trouble
stVal
3
GndRis
instMag
instMag.f
mag
mag.f
units
units.SIUnit
units.multiplier
db
zeroDb
InjVol
instMag
instMag.f
mag
mag.f
units
units.SIUnit
units.multiplier
db
zeroDb
InjAmp
instMag
instMag.f
mag
mag.f
units
units.SIUnit
units.multiplier
db
zeroDb
SHAmpAng
instMag
instMag.f
mag
mag.f
units
units.SIUnit
units.multiplier
3-104
LDevice inst: Prot
UR element: Sub-harmonic stator ground overcurrent functions
Type
FC UR Name
ACD
BOOLEAN
ST
SH STAT GND OC PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
SH STAT GND OC OP
SPS
BOOLEAN
ST
SH STAT GND OC DPO
SPS
BOOLEAN
ST
SH STAT GND TRB OP
MV
AnalogueValue
MX
FLOAT32
STATOR GND. RESIST
AnalogueValue
MX
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
SubHaPHIZ1.GndRis.db
INT32U
CF
MV
AnalogueValue
MX
FLOAT32
SH INJECTION VOLTS
AnalogueValue
MX
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
SubHaPHIZ1.InjVol.db
INT32U
CF
MV
AnalogueValue
MX
FLOAT32
SH INJECTION AMPS
AnalogueValue
MX
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
SubHaPHIZ1.InjAmp.db
INT32U
CF
MV
AnalogueValue
MX
FLOAT32
SH CURRENT ANGLE
AnalogueValue
MX
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
CHAPTER 3: IEC 61850 COMMUNICATION
Description
SH STAT GND OC PKP operand
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
SH STAT GND OC OP operand
SH STAT GND OC DPO operand
SH STAT GND TRB OP operand
STATOR GND. RESIST in kilo ohms
instMag.f deadbanded
30, the code for ohm
3, the code for a multiplier of kilo
0
SH INJECTION VOLTS in volts
instMag.f deadbanded
29, the code for volts (W/A)
0, the code for a multiplier of 1
0
SH INJECTION AMPS in amperes
instMag.f deadbanded
5, the code for ampere (A)
0, the code for a multiplier of 1
0
SH CURRENT ANGLE in degrees
instMag.f deadbanded
9, the code for degrees (deg)
0, the code for a multiplier of 1
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R

Advertisement