CHAPTER 3: IEC 61850 COMMUNICATION
LNName: AuxUvPTUV#
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.5 B90 breaker failure (B_BFai)
This element is instantiated in the following products: B90.
Table 3-23: B90 breaker failure current data objects
LNName: B_BFaiPIOC#
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
OpHiSet
ACT
general
BOOLEAN
OpLoSet
ACT
general
BOOLEAN
Table 3-24: B90 breaker failure logic data objects
LNName: B_BFaiRBRF#
data obj. data attribute
Type
OpEx
ACT
general
BOOLEAN
OpIn
ACT
general
BOOLEAN
BkrOp&
SPS
stVal
BOOLEAN
InRefγ01
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRefγ02
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRefγ03
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRefγ04
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRefγ05
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRefγ06
ORG
setSrcRef
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Auxiliary Undervoltage element# functions
FC UR Name
ST
AUX UV# OP
ST
AUX UV# DPO
AUX UV# BLOCK for group γ.
LDevice inst: Prot
UR element: B90 BREAKER FAILURE CURRENT SUPV # function
FC UR Name
ST
BKRSUPV # SUPV OP
ST
BKRSUPV # HISET OP
ST
BKRSUPV # LOSET OP
LDevice inst: Prot
UR element: B90 BREAKER FAILURE logic element
FC UR Name
ST
BKRFAIL # TRIP OP
ST
re-trip operand BKRFAIL #
RETRIP
ST
BKRFAIL # T& OP
BF# INITIATE for group γ.
BF# AMP SUPV OP A for group γ.reference to the data attribute to input
BF# AMP SUPV OP B for group γ.reference to the data attribute to input
BF# AMP SUPV OP C for group γ.reference to the data attribute to input
BF# BKR POS1 for group γ.
BF# BKR POS2 for group γ.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
AUX UV# OP operand
AUX UV# DPO operand, which is the
inverse of AUX UV PKP
AUX UV# BLOCK setting for setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
BKRSUPV # SUPV OP operand
BKRSUPV # HISET OP operand
BKRSUPV # LOSET OP operand
Description
BKRFAIL # TRIP OP operand
BKRFAIL # RETRIP operand
BKRFAIL # T& OP operand
BF# INITIATE setting for setting group γ. R
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# AMP SUPV OP A setting for setting
group γ.
source GoCB of input if via GOOSE
BF# AMP SUPV OP B setting for setting
group γ.
source GoCB of input if via GOOSE
BF# AMP SUPV OP C setting for setting
group γ.
source GoCB of input if via GOOSE
BF# BKR POS1 setting for setting group γ. R
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS2 setting for setting group γ. R
reference to the data attribute to input
R/W/C
R
R
R
R
R
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R/C
R/C
R/C
3-39