GE B30 Communications Manual page 311

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: MotThmPTTR1
data obj. data attribute
Type
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
TotLOTm
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
Analogue Value MX
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
3.5.2.38 Negative sequence directional overcurrent (NegDoc)
This element is instantiated in the following products: C70, D30, D60, F60, G30, G60, L60, L90, T60.
Table 3-68: Negative sequence directional overcurrent data objects
LNName: NegDocRDIR#
data obj. data attribute
Type
Dir
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
FwdOp
SPS
stVal
BOOLEAN
RvOp
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.39 Negative sequence instantaneous overcurrent (NegIoc)
This element is instantiated in the following products: C70, D30, D60, F35, F60, L30, L60, L90, T60.
Table 3-69: Negative sequence instantaneous overcurrent
LNName: NegIocPIOC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: THERMAL MODEL element
FC UR Name
instMag.f on deadband
exception
CF
CF
MotThmPTTR1.BiasMotLod.db
CF
MX
TOTAL MOTOR LOCKOUT TIME
instMag.f on deadband
exception
CF
CF
MotThmPTTR1.TotLOTm.db
CF
LDevice inst: Prot
UR element: Negative sequence Directional Overcurrent element #
FC UR Name
ST
logical OR of operands NEG DIR
OC# FWD and NEG DIR OC# REV
ST
ST
NEG SEQ DIR OC# FWD
ST
NEG SEQ DIR OC# REV
NEG SEQ DIR OC# BLOCK for
group γ.
LDevice inst: Prot
UR element: Negative sequence Instantaneous Overcurrent element #
FC UR Name
ST
NEG SEQ IOC# PKP
ST
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
1, the code for dimensionless
0, the code for a multiplier of 1
0
TOTAL MOTOR LOCKOUT TIME in seconds R
4, the code for Time (Sec)NOTE: Modbus
measures this value in Minute
0, the code for a multiplier of 1
0
Description
NEG DIR OC# FWD or NEG DIR OC# REV
operands, which becomes On when
Negative sequence directional
overcurrent is flowing in either forward or
reverse direction respectively
1 for forward 2 for backward 0 for none 3
for both
NEG SEQ DIR OC# FWD operand
NEG SEQ DIR OC# REV operand
NEG SEQ DIR OC# BLOCK setting for
setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
NEG SEQ IOC# PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
NEG SEQ IOC# OP operand
R/W/C
R
R
R
R
R/W/C
R
R
R
R
R
3
R
R
R
R/W/C
R
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
3-73